Square D > On-line Catalog > Products > 03 Molded Case Circuit Breakers and Enclosures > Ground-fault Protection: Micrologic® Add-on Ground-fault Module (GFM)and Ground Censor® Type GA—600 Vac

Supplemental and Obsolescence Digest 174

navigation start Table of Contents Previous Next Index end navigtion
Square D


Ground-fault Protection

Micrologic® Add-on Ground-fault Module (GFM)
and Ground Censor® Type GA—600 Vac

Class 931, 940, 960

Micrologic® Add-on Ground-fault Module (GFM)

The Micrologic ground-fault module (GFM) is a UL Listed circuit breaker accessory for equipment protection. It is a combination ground-fault relay and ground-fault sensing device.
Used in combination with the FA, KA, FC, KC, FI, and KI type circuit breakers with a ground-fault shunt trip factory installed (add the suffix “G” to the circuit breaker)
All GFMs supplied for I-Line® mounting, easily convertible to unit mount by removing the
I-Line brackets
Zone-selective interlocking capability is standard with upstream Micrologic trip system circuit breakers. The GFM can also be zone interlocked with the GC ground-fault system by using a restraint interface module.See Supplementary Digest
Companion
Circuit Breaker
Prefix
Ground-fault
Pickup Adjustment
Range
FAL, FHL, FCL,
FA, FH, FC
20–100 A
20–100 A
2833.00
KAL, KHL, KI,
KA, KH, KC
40–200 A
2833.00
Factory installed only. See Digest page 7-55.
20–100 A
2833.00
40–200 A
2833.00
a
Use NEMA 1 or 3R enclosures only. See page 3-36 for dimensions.

Ground-Censor® Type GA—600 Vac

The Type GA Ground-Censor equipment ground-fault protection system is recommended for protection of motor branch circuits. The type GA system is not recommended for service entrance applications, see GC200 in Section 7 of the Digest. The GA system requires the following components: GA relay, GA sensor, and circuit interrupter with 120 Vac shunt trip. GA test panel is optional, however sensor selected must be compatible with test panel when one is useda.

Consider substituting GC-200 or Vigirex® ground-fault relays.

Type GA System Features:

Ground-fault current pickup adjustable from 4–1200 A, dependent on the sensor used and the connections
Table 3.87:
 (for motor starter applications)
4–12, 12–36 A
4–12 A
4–12 A
25–75, 50–150, 150–450, 400–1200 A
50–150, 150–450, 400–1200 A
150–400, 400–1200 A