Ground-fault Protection
Micrologic® Add-on Ground-fault Module (GFM)
and Ground Censor® Type GA—600 VacClass 931, 940, 960
Micrologic® Add-on Ground-fault Module (GFM)
The Micrologic ground-fault module (GFM) is a UL Listed circuit breaker accessory for equipment protection. It is a combination ground-fault relay and ground-fault sensing device.
● Used in combination with the FA, KA, FC, KC, FI, and KI type circuit breakers with a ground-fault shunt trip factory installed (add the suffix “G” to the circuit breaker)
● All GFMs supplied for I-Line® mounting, easily convertible to unit mount by removing the
I-Line brackets
●
● Zone-selective interlocking capability is standard with upstream Micrologic trip system circuit breakers. The GFM can also be zone interlocked with the GC ground-fault system by using a restraint interface module.See Supplementary Digest
Table 3.86: FAL, FHL, FCL,
FA, FH, FC 20–100 A 20–100 A KAL, KHL, KI,
KA, KH, KC 40–200 A Factory installed only. See Digest page 7-55. 20–100 A 40–200 A
a Use NEMA 1 or 3R enclosures only. See page 3-36 for dimensions.Ground-Censor® Type GA—600 Vac
The Type GA Ground-Censor equipment ground-fault protection system is recommended for protection of motor branch circuits. The type GA system is not recommended for service entrance applications, see GC200 in Section 7 of the Digest. The GA system requires the following components: GA relay, GA sensor, and circuit interrupter with 120 Vac shunt trip. GA test panel is optional, however sensor selected must be compatible with test panel when one is useda.
Consider substituting GC-200 or Vigirex® ground-fault relays.Type GA System Features:
● Ground-fault current pickup adjustable from 4–1200 A, dependent on the sensor used and the connections
●
Table 3.87: 4–12, 12–36 A4–12 A4–12 A25–75, 50–150, 150–450, 400–1200 A50–150, 150–450, 400–1200 A150–400, 400–1200 A
|
|