Special Construction Circuit Breakers
Grounded BØ Systems
Class 600
Circuit Breakers for Grounded B-Phase (BØ) (Corner-grounded Delta) Systems (No Additional Charge)
Ordering Information For Grounded BØ Circuit Breakers
2. For use on 480 V systems, FH, KH, LH and MH type circuit breakers must be ordered as 600 V versions and with a 5861 suffiix (i.e. FHL361005861).
3. For use on 240 V systems, FH type circuit breakers may be ordered as 480 V versions with a 5861 suffix (i.e. FHL341005861).
4.
5. Two-pole 240 V grounded B-phase circuit breakers (except EDB, EGB, EJB, QB, QD, QG, and QJ) will be built using three-pole modules.
6. Two-pole grounded BØ circuit breakers will be labeled with 240 Vac interrupting ratings. Three-pole grounded BØ circuit breakers will be labeled with 480 Vac interrupting ratings.
7.
Table 3.58: Application Data for 240 Vac 3Ø Corner-grounded Delta System 240 Vac Interrupting Rating 15–100 A 70–250 A 15–125 A 15–150 A 18 kA, 35 kA,
65 kA, 100 kA 150–250 A 15–100 A 70–250 A 125–400 A 300–1000 A 300–800 A 600–1200 A 1200–2500 A 1200–2500 A 300–800 A 600–1200 A PG, PK Micrologic® Trip Unit 250–1200 A 600–1200 A 250–1200 A 1200–2500 A 600–2500 A 1200–2500 A 600–2500 A 1200–2500 A 600–2500 A
c Electronic = ET1.0 Electronic Trip System
Micrologic = 3.0, 5.0, 3.0A, 5.0A, 6.0A, 5.0P, 6.0P, 5.0H and 6.0 H Micrologic Trip System.
![]()
Three-pole circuit breakers must be used on three-phase 480 V corner-grounded delta systems. The outside poles are to be connected to the ungrounded phase and the grounded conductor connected to the center pole. Connecting the circuit breaker in a manner other than that described or shown may result in an unsafe application of the circuit breaker.
Table 3.59: 480 Vac Interrupting Rating 15–150 A 150–250 A 15–100 A 70–250 A 125–400 A 300–1000 A 300–800 A 600–1200 A PG, PK Micrologic Trip Unit 250–1200 A 600–1200 A 250–1200 A 1200–2500 A 600–2500 A 800–1200 800–6000
e Electronic = ET1.0 Electronic Trip System
Micrologic = 3.0, 5.0, 3.0A, 5.0A, 6.0A, 5.0P, 6.0P, 5.0H and 6.0 H Micrologic Trip System.
|
|