Table 24.1:
Maximum
Voltage
Maximum
Currentb
Blocks per ft
Std. Pack a
Std.
Pack a
Solderless Box Lug
for #22 to #8 AWG wire.
Mounts on standard 9080GH
track or 35 mm DIN 3 track.
1.60
0.52
1 #8
#10
1–3 #12
1–4 #14
1–4 #16
1–5 #18
1–8 #20
1–10 #22
Similar to a 9080GR6 except with
a 9080GH91 banana test plug
adapter installed.
1.90
0.52
Solderless Box Lug
for #22 to #10 AWG wire.
Can be mounted directly
to a panel or can be
mounted on 9080GH track.
1.60
0.62
1–4 #16
#10
1–2 #12
1–2 #14
1–4 #16
1–5 #18
1–8 #20
1–10 #22
High Density
Solderless Box Lug
for #22 to #10 AWG wire.
Mounts on standard
9080GH track or
35 mm DIN 3 track.
1.20
0.52
1 #10
#12
#14
1–2 #16
1–2 #18
1–5 #20
1–8 #22
1–2 #16
Solderless Box Lug
for #18 to #4 AWG wire.
Mounts on standard 9080GH
track or 35 mm DIN 3 track.
3.30
0.85
1 #4
#6
1–2 #8
1–4 #10
1–5 #12
1–6 #14
1–6 #16
1–8 #18
Solderless Box Lug
for #12 to #1/0 AWG wire.
Mounts on standard 9080GH
track or 35 mm DIN 3 track.
6.70
1.10
1 1/0
#1
#2
1–2 #4
1–3 #6
1–5 #8
1–6 #10
1–7 #12
Solderless Box Lug
for #6 AWG to 250 kcmil wire. d
Mounts on standard 9080GH
track or 35 mm DIN 3 track.
18.00


250 kcmild
1 4/0
3/0
2/0
1/0

1 #1
#2
#4
#6

b
These maximum current values assume the use of insulated copper conductors with 75oC temperature rating, and are calculated based on NEC Article 310, Table 310-16. In most cases this value is the maximum ampacity of that wire or combination of wires (as listed in the above table) which has the greatest current carrying capacity. The actual allowable current for a particular application depends on the number, size, insulation class, and other characteristics of the wires used. The lower of the UL and CSA ratings are shown.