Section - Page
|
Phase Failure Relays
Type MP
Class 8430 / Refer to Catalog 8430CT9701
The Class 8430 phase failure relays offer the reliability and accuracy of solid state circuitry with the isolation of hard output contacts.Phase Loss: This condition occurs when one line of a 3 phase system is completely lost.Phase Unbalance: This condition occurs when the voltage in one line of a 3 phase system drops below the voltage in the remaining two lines.Phase Reversal: This condition occurs when two of three lines in a 3 phase system are switched. This incorrect connection will cause a motor to rotate in the reverse direction.Undervoltage: This condition occurs when the voltage in all three lines of a 3 phase system drop simultaneously.
Contact
Arrangement Nominal Voltage Phase
Unbalance Phase
Reversal Under
Voltage Phase Failure and Undervoltage Relay
The Type MPS is a socket mounted, voltage sensing phase failure relay. The
undervoltage setting is adjustable from 75% to 100% of normal voltage. The
relay is UL Listed with the appropriate socket (see socket selection on
page 23-16). The 240 V rated, SPDT output contacts change state upon
phase failure, undervoltage, phase reversal or phase unbalance of 10% or
greater. Response time delay is 3 seconds. 240–60 480–60 Phase Failure and Undervoltage Relay
The Type MPD offers the same protection as the Type MPS plus the
following features: DPDT 600 V rated output contacts, locking potentiometer
undervoltage adjustment and an LED indicating “relay energized.” Can be
mounted directly to a panel or to 8501 XM track (see page 23-26). 120–60 240–60 480–60 600–60
Table 23.193:
File E42240 CCN NLDX provided the proper socket is used.
8430MPSV24 - 8501 NR51 or NR52 socket (see page 23-16).
8430MPSV29 - 8501 NR82 socket (see page 23-16).
Table 23.194: Make
VA Break
VA Make & Break
Amperes
Table 23.195: Voltage Code
- Related Topics
|
|
Release Date: 03/31/2007 |