Page 23-39
click here to download PDF version
Download PDF
Square D > On-line Catalog > Products > Relays and Timers > Phase Failure Relays: Type MP

navigation start Table of Contents Previous Next Index end navigtion
Square D


Digest 174 Quick Page Locator
Enter a page number from our paper catalog to go directly to that page in our online catalog.
Example: 5 - 3
Section - Page
-

Phase Failure Relays

Type MP

Class 8430 / Refer to Catalog 8430CT9701

Phase Loss: This condition occurs when one line of a 3 phase system is completely lost.
Phase Unbalance: This condition occurs when the voltage in one line of a 3 phase system drops below the voltage in the remaining two lines.
Phase Reversal: This condition occurs when two of three lines in a 3 phase system are switched. This incorrect connection will cause a motor to rotate in the reverse direction.
Undervoltage: This condition occurs when the voltage in all three lines of a 3 phase system drop simultaneously.
Table 23.192:
Contact
Arrangement
Nominal Voltage
Phase
Unbalance
Phase
Reversal
Under
Voltage
Phase Failure and Undervoltage Relay
The Type MPS is a socket mounted, voltage sensing phase failure relay. The
undervoltage setting is adjustable from 75% to 100% of normal voltage. The
relay is UL Listed with the appropriate socket (see socket selection on
page 23-16). The 240 V rated, SPDT output contacts change state upon
phase failure, undervoltage, phase reversal or phase unbalance of 10% or
greater. Response time delay is 3 seconds.
240–60
480–60
Phase Failure and Undervoltage Relay
The Type MPD offers the same protection as the Type MPS plus the
following features: DPDT 600 V rated output contacts, locking potentiometer
undervoltage adjustment and an LED indicating “relay energized.” Can be
mounted directly to a panel or to 8501 XM track (see page 23-26).
120–60
 488.00
240–60
480–60
600–60
Table 23.193:
+23oF to 122oF
-5oC to 50oC
File E42240 CCN NLDX provided the proper socket is used.
8430MPSV24 - 8501 NR51 or NR52 socket (see page 23-16).
8430MPSV29 - 8501 NR82 socket (see page 23-16).
File E42240 CCN
NLDX2 without using
the sockets listed.
Table 23.194:
Maximum
Control
Circuit
Voltage
Thermal
Continuous
Current
5
5
5
5
2.5
2.5
Table 23.195:
Discount Schedule

Related Topics

navigation start Table of Contents Previous Next Index end navigtion


Release Date: 03/31/2007
Modification Date: 04/13/2008