Page 22-9
click here to download PDF version
Download PDF
Square D > On-line Catalog > Products > Pressure, Vacuum, and Float Switches > Vacuum Switches: Types GAW and GVG

navigation start Table of Contents Previous Next Index end navigtion
Square D


Digest 174 Quick Page Locator
Enter a page number from our paper catalog to go directly to that page in our online catalog.
Example: 5 - 3

Section - Page
-

Vacuum Switches

Types GAW and GVG

Class 9016 / Refer to Catalog 9012CT9701

Type GAW

Sensitive Control Applications

GAW switches are provided with double throw contacts; normally open and normally closed circuits allow these controls to be used for standard or reverse action applications.

Standard devices can be mounted from the front with the bracket provided. Two mounting screws will be required for a firm attachment to any smooth, flat surface. Allowance must be made for flange projection. Controls with Form F modification include two mounting feet with 9/32" mounting holes on 3-3/4" centers. Range and Differential adjustments are internal and exposed by removal of the front cover.
File E12443
CCN NOWT
File LR25490
Type GAW ONLY
Maximum allowable positive pressure: 100 psig.
Diaphragms are oil resisting, nitrile butadiene rubber (BUNA N).
Electrical Ratings and Temperature Limitations—See page 22-2 for Type G machine tool.
Range on
Decreasing Vacuum
(In. of Hg)
Adjustable Differential
Adds to Rangea
(In. of Hg)
Contact
Arrangement
Pipe
Tap
(NPTF)
0–28.7
1 N.O.–1 N.C.
1/4 "-18
0–25
5–20
1 N.O.–1 N.C.
1/4 "-18
0–28.3
2 N.O.–2 N.C.
1/4 "-18
0–25
5–20
2 N.O.–2 N.C.
1/4 "-18
Table 22.23:
VITON® diaphragm
Table 22.24:
3–8
16.5–25
17–22
18–23
20–25

Type GVG

The Class 9016 Type GVG1 is designed as a companion to the Class 9036 Type GG and the Class 9037 Type GG float switches in common use on vacuum heating pumps. Electrical ratings of float and vacuum switch types are equal.
Cut-out Range
(In. of Hg)
Approximate Adjustable Differential
(In. of Hg)
Cut-in Range
(In. of Hg)
Pressure
Connection
5–25
5–10
0–20
Table 22.26:
3-Way Lever—Nameplate marked: Float only—Vacuum and Float—Continuous (Factory Modification Only)
Reverse action—Normally open contacts
Discount Schedule

navigation start Table of Contents Previous Next Index end navigtion


Release Date: 03/31/2007
Modification Date: 1/17/2008