|
|
|||||
|
|
|||||
Square D > On-line Catalog >
Products
>
NEMA Contactors and Starters > Information: Thermal Unit Selection |
|
|
|
Section - Page
|
Thermal Unit Selection
Approximate Thermal Unit Selection Based On Horsepower and Voltage
General—Thermal units selected using approximate full load currents from the table below will provide a trip current between 101% and 125% of full load current for many 4-pole, single speed, normal torque, 60 Hz motors. Since full load current rating of different makes and types of motors vary so widely, these selections may not be suitable.Thermal units should be selected on the basis of motor nameplate full load current and service factor. Thermal unit sizes originally selected on an approximate basis should always be rechecked and corrected at the time of installation if required.Instructions:
3.Only Use This Table When Motor Full Load Current Is Not Known
Motor
Horsepower
![]()
These currents should not be used for selection of fuses, circuit breakers or wire sizes. See NEC tables 430-148 through 430-150. For motors rated 208-220 volts, use 230 V column. For motors rated 440 to 550 volts, use 460 and 575 V columns, respectively.Mounting Thermal Units
Always be certain the correct thermal units are installed in the starter before operating the motor. Thermal units should always be mounted so that their type designation can be read from the front of the starter (see Figure 1). Melting alloy thermal units should be mounted so that the tooth of the pawl assembly can engage the teeth of the ratchet wheel when the reset button is pushed.
|
|
Release Date: 03/31/2007 |