Page 16-129
click here to download PDF version
Download PDF
Square D > On-line Catalog > Products > NEMA Contactors and Starters > Information: Thermal Unit Selection

navigation start Table of Contents Previous Next Index end navigtion
Square D


Digest 174 Quick Page Locator
Enter a page number from our paper catalog to go directly to that page in our online catalog.
Example: 5 - 3
Section - Page
-

Thermal Unit Selection

General

All tables are based on the operation of the motor and controller in the same ambient temperature, 40oC (104oF) or less. Always be certain the correct thermal units are installed in the starter before operating the motor. Each thermal unit shall be installed such that its catalog number is visible. See page 16-133, Figure 1 for complete thermal unit installation instructions. On melting alloy thermal units the ratchet wheel must engage the pawl assembly.

Selection Procedure

Note: If motor full load current (FLC) is not known, a tentative thermal unit selection could be made, based on horsepower and voltage. Refer to page 16-133.
Motor and controller in same ambient temperature:
Motor and controller in different ambient temperatures:
See page 16-132 for calculation of trip current rating.

Slow Trip Thermal Unit Selection

To select Type SB slow trip thermal units, the selection table for a standard Type B thermal unit may be used with the following modifications: For continuous rated motors having service factors of 1.15 to 1.25, select thermal units from the standard Type B table using 93% (102% for Class 8198) of the full load current shown on the motor nameplate and then substitute an SB for the B in the thermal unit type number.
Example: A motor with a full load current of 12 amps controlled by an 8536SCG3 would require B22 thermal units for standard trip applications and SB19.5 thermal units for slow trip applications. The SB is selected by multiplying 12 amps times 93% for 11.16 amps and using this value to select B19.5. Then add the S prefix to arrive at SB19.5.
For continuous rated motors having a service factor of 1.0, select thermal units in the same manner using 84% (93% for Class 8198) of full load current shown on the motor nameplate.
*
SB thermal units are used on Size 0, 1, 2 and only some Size 3 applications. Check thermal unit tables for current ranges.
Class
of
Controller
Continuous
Duty
Motor
Service
Factor
Melting Alloy and
Non-Compensated
Bimetallic Relays
Ambient
Temp.-
Comp.
Relays
Same as
Controller
Ambient
Constant
10oC
(18oF)
Higher
Than
Controller
Ambient
Constant
10o C
(18oF)
Lower
Than
Controller
Ambient
Constant
40oC
(104oF)
or less,
for Any
Controller
Ambient
All
Classes,
Except
8198
 .95
Class
8198
Table 16.382:
Thermal
Unit Type
Thermal
Unit Type

Standard
Discount Schedule

navigation start Table of Contents Previous Next Index end navigtion


Release Date: 03/31/2007
Modification Date: 04/13/2008