Page 16-98
click here to download PDF version
Download PDF
Square D > On-line Catalog > Products > NEMA Contactors and Starters > Thermal Overload Relays—NEMA Rated: Solid State Overload Relay, Motor Logic and Motor Logic Plus

navigation start Table of Contents Previous Next Index end navigtion
Square D


Digest 174 Quick Page Locator
Enter a page number from our paper catalog to go directly to that page in our online catalog.
Example: 5 - 3
Section - Page
-

Thermal Overload RelaysNEMA Rated

Solid State Overload Relay, Motor Logic® and Motor Logic Plus

Class 9065 / Refer to Catalog 9065CT9701

Motor Logic

Base Unit relays feature: 3 to 1 adjustment for trip current; phase loss and unbalance protection; direct replacement for Type S melting alloy; and LED power indication. They are ambient insensitive and self–powered. Electrical remote reset is also available.
*
Motor Logic SSOLR are designed to protect 50/60 hertz three-phase AC motors from overload, phase unbalance and phase loss conditions. Open Delta systems or grounded B-phase systems are difficult to balance and could cause the Motor Logic SSOLR to trip. For applications of this nature, it is recommended that bi-metallic overload relays (Form B12) be used.
Table 16.285:
Base Unit: For Separate Mounting
Solid State Overload Relay
600 Vac Maximum
Full Load
Current Range
(Amperes)
00Ca
0a
1a
2
3
4
3–9
6–18
9–27
15–45
30–90
45–135
a
Size 00c, 0, and 1 are supplied without lugs. Lower amperage loads can be protected by looping of power wires. Lugs are available, see page 16-124.
Table 16.286:
Base Unit: Replacement SSOLR for Retrofit of Square D Type S Starter
Solid State Overload Relay
600 Vac Maximum
Full Load Current Range (Amperes)
2
6-18
9-27
45-135
90-270
90-270
b
Lug - Bar Kits are available for Size 00c, 0 and 1. Lower amperage loads can be protected by looping of power wires. See page 16-124.
c
Size 5 Replacement Overload is only for existing NEMA S starters with MOTOR LOGIC overload relay. External CTs and additional components are not included.
d
Size 5 is a complete drop-in replacement for Square D NEMA  S melting alloy, bimetallic, and Y500 overload relays only.
Feature Unit relays include all of the features found on the Base Unit relays plus: switch selectable trip class; Class II ground fault detection; and direct replacement for Type S melting alloy. Electrical remote reset is also available.
Table 16.287:
Feature Unit: For Separate Mounting Solid State Overload Relay
600 Vac Maximum
Full Load
Current Range
(Amperes)
00C
0
1
2
3
4
1.5–4.5f
3–9f
6–18f
9–27f
15–45
30–90
45–135
f
Size 00B, 00C, 0, and 1 are supplied without lugs. Lower amperage loads can be protected by looping of power wires. Lugs are available.
See page 16-124.
g
NEMA Size 00B and 00C are not actual NEMA sizes. These designations are used to differentiate the lower FLA of these devices from the NEMA Size 00 Motor Logic Solid State Overload Relay.
Table 16.288:
Feature Unit: Replacement SSOLR for Retrofit of Square D Type S Starter
Solid State Overload Relay
600 Vac Maximum
Full Load Current Range (Amperes)
00Bh
00Ch
0h
1h


1.5–4.5
3–9
6–18
9–27
15–45
30–90
45–135
90–270
90–270
180–540
270–810
h
Size 00B, 00C, 0, and 1 are supplied without lugs. Lower amperage loads can be protected by looping of power wires.
i
Size 5, 6 and 7 Replacement Overloads are only for existing NEMA S starters with MOTOR LOGIC overload relay. External CTs and additional components are not included.
j
Size 5 is a complete drop-in replacement for Square D NEMA S melting alloy, bimetallic, and Y500 overload relays only.
k
NEMA Size 00B and 00C are not actual NEMA sizes. These designations are used to differentiate the lower FLA of these devices from the NEMA Size 00 Motor Logic Solid State Overload Relay.

Motor Logic Plus

Motor Logic Plus solid state overload relay is separately powered and fully programmable. It is designed to protect 200–480 Vac or 600 Vac, 3-phase AC motor applications. The SSOLR has one Form C relay output rated for 300 Vac maximum.
Table 16.289:
Product
Description Current Range
0.5–2.3 A
2.0–9.0 A
6.0–27.0 A
10.0–45.0 A
20.0–90.0 A
60.0–135.0 A
120.0–270.0 A
240.0–540.0 A
Table 16.290:
0.5–2.3 A
2.0–9.0 A
6.0–27.0 A
10.0–45.0 A
20.0–90.0 A
60.0–135.0 A
120.0–270.0 A
240.0–540.0 A

Example

Motor Logic Plus overload relay with a current range of 6–27 A and modifications to add communication module for an open style starter package.
See pages 16-10116-102 for dimensions.
Discount Schedule

navigation start Table of Contents Previous Next Index end navigtion


Release Date: 03/31/2007
Modification Date: 04/13/2008