Page 16-92
click here to download PDF version
Download PDF
Square D > On-line Catalog > Products > NEMA Contactors and Starters > AC Duplex Motor Controllers: 3-Pole Polyphase Non-Combination Type

navigation start Table of Contents Previous Next Index end navigtion
Square D


Digest 174 Quick Page Locator
Enter a page number from our paper catalog to go directly to that page in our online catalog.
Example: 5 - 3
Section - Page
-

AC Duplex Motor Controllers

 

Class 8941

Duplex Motor Controllers are used to control two motors, and consist of two starters in a common enclosure. Two separate disconnect switches or circuit breakers with operators are included with all combination devices. Unless Form Y68 is specified, an alternation circuit (a Class 8501 Type XO40 relay) is included, which alternately operates first one motor and then the other on each successive closing of a pilot device. Both motors will be energized should a second pilot device close. All devices incorporate a terminal block to simplify wiring of pilot devices A and B. Typical applications include pump motors where a second pump is required for peak demand periods yet alternation is desirable to equalize pump wear.
Table 16.259:
3-Pole Polyphase—600 Vac Maximum (50–60 Hz)
Non-Combination Type—Without Disconnect—With Electric Alternation
Note that the prices shown do not include thermal units. Devices require 6 thermal units.
Standard trip thermal units are $14.30 each. See page 16-129 for selection information.
NEMA
Size
Maximum
Rating
Each
Motor
NEMA 1
General
Purpose
Enclosure
NEMA 4/4X
Watertight
and Dusttight
Enclosure
Stainless Steel
NEMA 12
(NEMA 3 and 3R) a
Dusttight and
Driptight Industrial Use
Enclosure
Open
Type
Hp
Polyphase
200–230
460–575
3
5
200–230
460–575
7-1/2
10
200
230
460–575
10
15
25
200
230
460–575
25
30
50
460–575
40
50
Table 16.260:
3-Pole Polyphase—600 Vac Maximum (50–60 Hz)
Combination Thermal Magnetic Circuit Breaker Type—With Electric Alternation
Note that the prices shown do not include thermal units. Devices require 6 thermal units. Standard trip thermal units are $14.30 each. See page 16-129 for selection information.
Motor
Starter
Voltage
Max.
Hp
Poly-
phase
Coil
Voltage
NEMA
Size
Circuit
Breaker
NEMA 1
General Purpose
Enclosure
NEMA 4/4X
Watertight and Dusttight
Stainless Steel Enclosure
NEMA 12
(NEMA 3
and 3R)a
Dusttight and Driptight
Industrial Use Enclosure
Frame
Size
Ampere
Rating
200
(208)
  2
  3
208–60
 15
 20
  5
  7-1/2
 35
 50
10
 60
15
20
25
FAL
FAL
KAL
 90
100
110
30
40
230
(240)
  2
  3
240–60
220–50
 15
 20
  5
  7-1/2
 30
 45
10
15
 60
 80
25
30
FAL
KAL
100
110
40
50
150
200
460
(480)
  5
480–60
440–50
 15