Square D > On-line Catalog >
Products
>
NEMA Contactors and Starters > WELL-GUARD Pump Panels: Full Voltage Type, Type NS, SS, XS |
|
|
|
Section - Page
|
WELL-GUARD® Pump Panels
Full Voltage Type, Type NS, SS, XS
Class 8940 / Refer to Catalog 8940CT9701
![]()
Motor Logic SSOLR are designed to protect 50/60 hertz three-phase AC motors from overload, phase unbalance and phase loss conditions. Open Delta systems or grounded B-phase systems are difficult to balance and could cause the Motor Logic SSOLR to trip. For applications of this nature, it is recommended that bi-metallic overload relays (Form B12) be used.Class 8940 Type NS, SS, and XS panels in NEMA 3R enclosures are specifically designed for pumping applications. Extra space is provided for field installation of auxiliary equipment.
● Class 10 Motor Logic® SSOLR through 200 hp–480 V, 100 hp–240 V, Type SS only
● Phase failure sensitive through 200 hp–480 V, 100 hp–240 V, Type SS only
Table 16.249: 3-Pole Polyphase—480 Vac Maximum (50–60 Hz)—Fusiblea Maximum Hp
Polyphase Coil
Voltage 240–60220–50 480–60440–50
Table 16.250: 3-Pole Polyphase—480 Vac Maximum (50–60 Hz)—Circuit Breaker Max. Hp
Polyphase 240–60
220–50 480–60
440–50
a To substitute an IEC ambient compensated bimetallic overload relay (up to size 5) for the MOTOR LOGIC SSOLR, request Form B12 and state motor hp
(no charge). This applies to the above (SSx) devices only.
e Circuit breaker disconnect supplied. (See page 7-31 for circuit breaker adjusment range.)
Table 16.251: Class 8940—UL Listed Short Circuit Ratings NEMA
Size Available Amperes
RMS Symmetrical
Table 16.252: Class 8940—UL Listed Short Circuit Ratings NEMA Fuse
Class 0–3 0–3 0–2 0–2 4–5 4–5
|
|
Release Date: 03/31/2007 |