A squirrel cage motor draws high starting current (inrush) and produces high starting torque when started at full voltage. While these values differ for different motor designs, for a typical NEMA design B motor, the inrush will be approximately 600% of the motor full load amperage (FLA) rating and the starting torque will be approximately 150% of full load torque at full voltage. High current inrush and starting torque can cause problems in the electrical and mechanical systems, or may even damage the materials being processed.
When a motor is started at reduced voltage, the current at the motor terminals is reduced in direct proportion to the voltage reduction while the torque is reduced by the square of the voltage reduction. If the “typical” NEMA B motor is started at 70% of line voltage, the starting current would be 70% of the full voltage value (that is, 0.70 x 600% = 420% FLA). The torque would then be (0.70)
2 or 49% of the normal starting torque (that is, 0.49 x 150% = 74% Full Load Torque). Therefore, reduced voltage starting provides an effective means of reducing both inrush current and starting torque.
If the motor has a high inertia or if the motor rating is marginal for the applied load, reducing the starting torque may prevent the motor from reaching full speed before the thermal overloads trip. Applications that require high starting torque should be reviewed to determine if reduced voltage starting is suitable.
Square D offers several types of electromechanical as well as solid state reduced voltage starters that provide different starting characteristics. The following describes the 8600 series of reduced voltage starters.
Autotransformer starters provide reduced voltage to the motor terminals during starting through the use of a tapped, three phase autotransformer. Taps on the autotransformer allow for selection of the motor with 50%, 65% or 80% of line voltage values supplying 50%, 65% or 80% of the current inrush seen during a full voltage start. The resulting starting torque will be 25%, 42% or 64% of full voltage values, as will be the current draw on the line. Thus, the autotransformer provides the maximum torque with minimum line current.
Wye-delta starters can only be used on wye-delta motors which have six leads that allow for motor winding to be connected in either a wye or delta configuration. During start up, the windings are connected in the wye resulting in 58% of line voltage applied across two windings. This reduces both inrush and starting torque to 33% of the delta connected values. After a set time delay, the motor leads are switched to the delta connection.
The wye-delta starter is available in both open and closed transition configurations. Closed transition starters are supplied with an additional contactor and resistor bank used to keep the motor windings energized for a few cycles until the transition from wye to delta is complete.
Part winding starters can only be used with part winding motors. During a part winding start, only one winding is energized, which reduces the inrush current to 60–70% (depending on the motor design) and starting torque to 50% of normal starting values with both windings energized. Most (but not all) dual voltage 230/460 volt motors are suitable for part winding starts at 230 volts.