Combination Starters—NEMA Rated
Class 8538, 8539 / Refer to Catalog 8538CT9701
Application Data
Table 16.91: Class 8539—UL Listed Short Circuit Ratings MAG-GARD® Motor Circuit Protector Type Available Amperes
RMS Symmetrical 0–480 0–480 481–600 481–600 0–2 with Current Limiting Module 0–3 with Current Limiting Module 0–3 2–6 0–480 481–600
Table 16.92: Suffix
Number Range
(A) Suffix
Number Range
(A) Suffix
Number Range
(A) Suffix
Number Range
(A) 9–33 8–28 625–1250 1500–3000 21–77 18–70 750–1500 1750–3500 45–165 50–180 875–1750 2000–4000 90–330 100–350 1000–2000 2500–5000 150–550 150–580 1125–2250 3000–6000 225–825 300–1100 1250–2500 3500–7000
![]()
The MAG-GARD adjustable trip range is determined by the suffix of the circuit breaker catalog number. Table 16.92 indicates the trip range which corresponds to a given suffix number. The MAG-GARD Motor Circuit Protector should be adjusted to a level just above Locked-Rotor Current of the motor. This setting will provide optimum overcurrent protection for the motor. For more information on MAG-GARD instantaneous trip circuit breakers, refer to the MAG-GARD circuit breaker section of this Catalog.
Table 16.93: Class 8539—UL Listed Short Circuit Ratings NEMA
Size Available Amperes
RMS Symmetrical
Table 16.94: Class 8538—UL Listed Short Circuit Ratings NEMA Fuse
Class 0–3 0–3 0–2 0–2 4–5 4–5
Table 16.95: 3/4–1-1/2 2–3 5–25 30–125
![]()
The combination starter selection tables on pages 16-34–16-35 are suitable for motors with Locked-Rotor Current letters per NEC Table 430-7(b) as listed in Table 16.95. For other motors a special thermal magnetic circuit breaker with adjustable magnetic trip settings for the specific motor is required. When ordering for these special applications, specify the motor horsepower, voltage, frequency, full load current and code letter (or locked rotor current) to assure proper protection.
Table 16.96: NEMA
Size Type of
Lug Type of
Lug Wires Per
Terminal Type of
Lug