Page 11-8
click here to download PDF version
Download PDF
Square D > On-line Catalog > Products > Switchboards and Switchgear > Switchgear: Medium Voltage Metal-Enclosed —HVL/cc

navigation start Table of Contents Previous Next Index end navigtion
Square D


Digest 174 Quick Page Locator
Enter a page number from our paper catalog to go directly to that page in our online catalog.
Example: 5 - 3

Section - Page
-

Switchgear

Medium Voltage Metal-Enclosed —HVL/cc™

Class 6045 / Refer to Product Data 6040PD9601 or Handout 6040HO9501

HVL/cc Metal-Enclosed Load Interrupter Switchgear—Full Range

The Square D® HVL/cc metal-enclosed load interrupter switchgear provides switching, metering, and interrupting capabilities for medium voltage electrical power distribution systems and is designed and tested per applicable ANSI/IEEE and NEMA standards.

Made up of modular units, the HVL/cc is easy to expand. Two main bus positions allow future extensions and connections to existing equipment.

HVL/cc switchgear is available in either single or multiple bay units. The design is compact, with front accessibility.
The HVL/cc switch can be equipped with either an over-toggle mechanism (OTM), which is standard, or an optional stored energy mechanism (SEM). An option with both mechanisms is the Fuselogic™ system. The Fuselogic system offers fuse tripping (with SEM) to provide protection against single phasing loads when a fuse has blown. It also has a mechanical interlock to prevent inadvertent switching until fuses have been installed or blown fuses have been replaced.

The HVL/cc enclosure is designed for front access only and can be positioned against walls, in small rooms or in pre-fabricated buildings. The small footprint can result in considerable cost savings from the reduction of building or room sizes.
HVL/cc Load Interrupter Switches— Full Range 600/1200 Ampere Ratings
Switch (kV)
maximum design
Fault close
(kA asymmetrical)
Momentary current
(kA asymmetrical)
Short time current
(kA symmetrical)
Electrical endurance (number of operations at 80% P.F.)
Mechanical endurance (number of operations)

Switch Standard Features

Switch Positions: Closed, open, and internally grounded (optional) (connects switch contacts to ground)
5.8 PSI (£ 17.5 kV)
22 PSI (25.8–38 kV)

Options

Powerlogic® metering

Fuselogic™

Fuselogic is a protection system that provides the ultimate in medium voltage fuse protection. This patented system utilizes the Square D® current-limiting fuses with mechanical sensors that function without any auxiliary power requirements. Several combinations of Fuselogic functions can be combined to provide simple blown fuse indication contacts with mechanical lockout to anti-single phasing protection. Anti-single phasing requires the optional stored energy mechanism (SEM). Fuselogic is available on both HVL/cc and HVL switches.

Switchgear Standard Features

Surge Arresters
Effectively
Grounded
Neutral Circuits
Impedance Grounded
and Ungrounded
Circuits
2.4
4.16
4.8
6.9
12.0
2.54
4.4
5.08
7.26
12.7

2.55


7.65
2.55
5.1
5.1
7.65
12.70
12.47
13.2
13.8
13.2
13.97
14.52
7.65
8.4
8.4
12.70