Page 11-6
click here to download PDF version
Download PDF
Square D > On-line Catalog > Products > Switchboards and Switchgear > Switchgear: Low Voltage Metal-Enclosed Drawout

navigation start Table of Contents Previous Next Index end navigtion
Square D


Digest 174 Quick Page Locator
Enter a page number from our paper catalog to go directly to that page in our online catalog.
Example: 5 - 3

Section - Page
-

Switchgear

Low Voltage Metal-Enclosed Drawout

Class 6037 / Refer to Catalog 6037CT9901

Power-Zone® 4 Low Voltage Switchgear with Masterpact® Circuit Breakers

The Square D® Power-Zone® 4 low voltage metal-enclosed drawout switchgear is designed to provide superior electrical distribution, protection, and power quality management. The prime components of the switchgear are the Masterpact® NW and NT ANSI rated circuit breaker. Power-Zone 4 switchgear is designed to maximize the functionality of the Masterpact circuit breakers, which, in turn, deliver maximum uptime, system selectivity, ease of maintenance, and reliable circuit protection. All of these features are packed into the smallest footprint available for low voltage drawout switchgear.
Power-Zone 4 is designed and built to ANSI® C37.20.1 and is Listed to UL® 1558
Masterpact NW and NT drawout low voltage power circuit breakers are designed and built to ANSI C37.13 and C37.16. Listed to UL 1066
Arc flash limiting Masterpact NW feeder breakers available in 800, 1600, and 2000 ampere ratings
Family of field installable and upgradeable Micrologic® trip units with optional Powerlogic® data communications features
Power-Zone 4 switchgear can offer optional Transparent Ready® Web-enabled data communications capability
Bolted copper bus provided as standard
(up to 5000 amperes maximum)
Available in NEMA 3R outdoor walk-in enclosures
Masterpact NW circuit breakers are available in various levels of interrupting ratings from 42–200 kA at 480 volts and 130 kA at 600 volts.
The Masterpact NT circuit breaker is available in an 800 ampere frame size and 42 kA at 480 volts interrupting rating. Up to 8 Masterpact NT circuit breakers can be mounted in a 30-inch wide section. (Not available for 600 volts.)
800
800

Micrologic® Trip Units

A modern family of field-installable trip units is available with Masterpact NW and NT circuit breakers. The circuit breaker overcurrent protection consists of a microprocessor-based tripping device that requires no external power source. The complete tripping system has three main components: the air-core sensors, the trip device (with rating plug), and the trip actuator. The microprocessor-based trip unit uses true RMS current level sensing.
The Powerlogic® system is used in conjunction with Micrologic Type A, Type P, and Type H trip units for the Masterpact NW and NT circuit breakers. Modbus® industry standard data communications allow the Powerlogic system to replace discrete meters, multiple transducers, analog wires, and analog-to-digital conversion equipment. Extensive information can be transmitted over a single communications cable to a Powerlogic system display, a personal computer, programmable logic controller, or other host system.
Basic circuit information, such as amperes, can be monitored using Micrologic Type A trip unit. Circuit breaker remote operation is available using the Micrologic Type P and Type H trip units with Powerlogic functionality. In addition to its metering capabilities, the Micrologic trip unit system is available with optional status inputs and relay outputs for monitoring discrete contacts and remote control of devices by way of the data communications channel.

navigation start Table of Contents Previous Next Index end navigtion


Release Date: 03/31/2007
Modification Date: 1/16/2008