Speed-D Switchboards
CTC Cabinets -- Wall Mounted Metering Equipmentf
Class 2730
Main Circuit Breaker and Current Transformer Compartment
Service Entrance Equipment Hot or Cold Sequence Metering, Top or Bottom Feed, Indoor Construction at 600 VoltsGeneral: Suitable for use as service entrance equipment on AC systems. Listed by Underwriters’ Laboratories.Service: 1Ø3W, 3Ø3W, 3Ø4W, rated up to 600 Vac maximum.Metering: a Current transformer compartment with provisions for installing bar type current transformers. For window type current transformers, order bus link kit from product selection table below.Standard unit is factory assembled for bottom feed cold sequence or top feed hot sequence metering applications. The unit is field convertible for bottom feed hot sequence or top feed cold sequence metering. Refer to Class 2730 Installation and Operation Bulletin for field conversion details.Mains: Main disconnects provided. 400-800 ampere: MJP. 1000-1200 ampere: PJP. Handle lock-off attachment provided for main circuit breaker as standard.Enclosure: Front accessible, totally enclosed, gray baked enamel finish. Available as indoor construction only. Dimensions—78"H x 26"W x 14.3"D.
Table 9.174: Service
Voltage (AC) Ampere Rating
of Main Bus Link Kit—Utilized when installing window type current transformers
Table 9.175: Ampere
Rating (3) 3/0–500 kcmil #6 AWG–300 kcmil (3) 3/0–500 kcmil (3) 3/0–500 kcmil (4) 3/0–500 kcmil (4) 3/0–500 kcmil
b Must specify feed (top or bottom) and sequence (hot or cold) at the time of order.
Ground fault protection—consists of ground fault relay, ground fault sensor, and display. Available only on 1000 A and 1200 A units.