Page 9-27
click here to download PDF version
Download PDF
Square D > On-line Catalog > Products > Panelboards > Circuit Breakers: I-LinePanelboards and Switchboards

navigation start Table of Contents Previous Next Index end navigtion
Square D


Digest 174 Quick Page Locator
Enter a page number from our paper catalog to go directly to that page in our online catalog.
Example: 5 - 3
Section - Page
-

Circuit Breakers

For I-Line® Panelboards and Switchboards

Class 660, 665, 670, 830

Table 9.121:
L-frame—400 A, I-Line® LA/LH MC
High Magnetic Withstand Circuit Breaker For Mission Critical Loads
Ampere
Rating
AC Magnetic
Level Factory Set b
Terminal
Wire
Range
one #4 AWG–350 kcmil
 3714.
 5847.
 3787.
 5921.
 4627.
 6761.
AL400LA
one #1 AWG–600 kcmil or
two #1 AWG–250 kcmil
Table 9.122:
L-frame—400 A, Thermal-magnetic (600 Vac)
Ampere
Rating
AC Magnetic
Trip Settings
Terminal
Wire
Range
 625
 750
 875
AL400LA
one #1 AWG–600 kcmil or
two #1 AWG–250 kcmil
 625
 750
 875
AL400LA
one #1 AWG–600 kcmil or
two #1 AWG–250 kcmil
Table 9.123:
L-frame—600 A, Thermal-magnetic (600 Vac)
Ampere
Rating
Terminal
Wire
Range
AL600LI5
two #4/0 AWG–500 kcmil
 5794.
 9299.
AL600LI5
two #4/0 AWG–500 kcmil
 6438.
b
AC magnetic setting tolerances are +0 -25% from maximum value shown.