Table 9.100:
F-frame—100 A, Thermal-magnetic (600 Vac)
Ampere
Rating
AC Magnetic
Trip Settings
Terminal
Wire
Range
 15
 20
 25
 30
 275
 275
 275
 275
 600
 600
 600
 600
  338.
  338.
  338.
#14–#4 AWG Cu or
#12–#4 AWG Al
 35
 40
 45
 50
 60
 70
 80
 90
 400
 400
 400
 400
 800
 800
 800
 900
 900
 850
 850
 850
 850
  338.
  338.
  338.
  338.
  338.
  375.
  375.
  375.
  375.
#14–#1/0 AWG Cu or
#12–#1/0 AWG Al
 15
 20
 25
 30
 275
 275
 275
 275
 600
 600
 600
 600
 520.
 520.
 520.
  809.
  809.
  809.
 1842.
#14–#4 AWG Cu or
#12–#4 AWG Al
 35
 40
 45
 50
 60
 70
 80
 90
 400
 400
 400
 400
 800
 800
 800
 900
 900
 850
 850
 850
 850
 520.
 520.
 520.
 520.
 520.
 631.
 631.
 631.
 631.
  809.
  809.
  809.
  809.
  809.
  968.
  968.
  968.
  968.
 1842.
 1842.
 1842.
 1842.
 1842.
 1842.
 1842.
#14–#1/0 AWG Cu or
#12–#1/0 AWG Al
 15
 20
 25
 30
 275
 275
 275
 275
 600
 600
 600
 600
 647.
 647.
 647.
  964.
  964.
  964.
 2306.
#14–#4 AWG Cu or
#12–#4 AWG Al
 35
 40
 45
 50
 60
 70
 80
 90
 400
 400
 400
 400
 800
 800
 800
 900
 900
 850
 850
 850
 850
 647.
 647.
 647.
 647.
 647.
 775.
 775.
 775.
 775.
  964.
  964.
  964.
  964.
  964.
 1088.
 1088.
 1088.
 1088.
 2306.
 2306.
 2306.
 2306.
 2306.
 2306.
 2306.
#14–#1/0 AWG Cu or
#12–#1/0 AWG Al
Table 9.101:
PowerPact® Q-frameb— 225 A, Thermal-magnetic (240 Vac)
Ampere
Rating
AC Magnetic
Trip Settings
70
80
400.
801.
1062.
1328.
90
400.
801.
1062.
1328.
400.
801.
1062.
1328.
400.
801.
1062.
1328.
400.
801.
1062.
1328.