Page 7-46
click here to download PDF version
Download PDF
Square D > On-line Catalog > Products > Miniature and Molded Case Circuit Breakers > Ground-fault Protection : VigirexTM Ground-fault Relay System

navigation start Table of Contents Previous Next Index end navigtion
Square D


Digest 174 Quick Page Locator
Enter a page number from our paper catalog to go directly to that page in our online catalog.
Example: 5 - 3
Section - Page
-

Ground-fault Protection

VigirexTM Ground-fault Relay System

Class 931, 840, 960

Vigirex™ Ground-Fault Relay System

The Vigirex ground-fault relays, with associated sensors (current transformers), measure the residual current in an electrical installation to detect levels which may be damaging. When used for protection, they cause an associated circuit breaker or switch to interrupt the supply of power to the protected system. They may also be used for monitoring only, with output to an alarm. The product line includes fixed sensitivities from 30 mA to 1 A and adjustable sensitivities up to 30 A.
The Vigirex relays may be easily mounted on DIN rail or may be panel mounted in a meter cutout. Sensors for conductors range from a little more than an inch diameter toroids, to large rectangular sensors measuring 6 x 18 inches. The compact size of the relay and its sensor make it ideal for protection of OEM equipment as well as branch circuits.
12–24 Vac/12–48 Vdc
110–130 Vac
1325.00
220–240 Vac
1325.00
Instantaneous
or 60 msec
(2 settings)
12–24 Vac/12–48 Vdc
30 mAa or 300 mA
(2 settings)
1575.00
110–130 Vac
220–240 Vac
Adjustable
(9 settings):
0, 0.06, 0.15,
0.23, 0.31, 0.5,
0.8, 1.0, 4.5 sec
12–24 Vac/12–48 Vdc
Adjustable,
(9 settings):
0.03a, 0.1, 0.3, 0.5, 1, 3, 5, 10, 30 A
1800.00
110–130 Vac
220–240 Vac
12–24 Vac/12–48 Vdc
1800.00
110–130 Vac
220–240 Vac
12–24 Vac/12–48 Vdc
1375.00
110–130 Vac
1375.00
220–240 Vac
1375.00
Instantaneous
or 60 mSec
(2 settings)
12–24 Vac/12–48 Vdc
30 mAa or 300 mA
(2 settings)
1625.00
110–130 Vac
220–240 Vac
Adjustable
(9 settings):
0, 0.06, 0.15,
0.23, 0.31, 0.5,
0.8, 1.0, 4.5 sec
12–24 Vac/12–48 Vdc
Adjustable
(9 settings):
0.03a, 0.1, 0.3, 0.5, 1, 3, 5, 10, 30 A
1875.00
110–130 Vac
220–240 Vac
12–24 Vac/12–48 Vdc
1875.00
110–130 Vac
220–240 Vac
a
30 mA is instantaneous only
Maximum
Current
325.00
410.00
555.00
835.00
1530.00