Page 7-31
click here to download PDF version
Download PDF
Square D > On-line Catalog > Products > Miniature and Molded Case Circuit Breakers > Motor Circuit Protectors : GJ-, LA-, and MA-frame MCP Selection

navigation start Table of Contents Previous Next Index end navigtion
Square D


Digest 174 Quick Page Locator
Enter a page number from our paper catalog to go directly to that page in our online catalog.
Example: 5 - 3
Section - Page
-

Motor Circuit Protectors

GJ-, LA-, and MA-frame MCP Selection

Class 680

Adjustable instantaneous-trip circuit breakers are intended for use in combination with motor starters with overload relays for the protection of motor circuits from short circuits. Other specific applications include rectifiers and resistance welders. These circuit breakers contain a magnetic trip element in each pole with the trip point adjustable from the front. Interrupting ratings are determined by testing the instantaneous-trip circuit breakers in combination with a contactor and overload relay.

Select instantaneous-trip circuit breakers as follows:
This selection table is suitable for motors, other than NEMA Design E, with locked-rotor indicating code letters per NEC® Table 430.7 (b) as follows:
A–L
A–K
A–J
A–H
A–G
A–F
1.
For other motors order a special thermal-magnetic circuit breaker with magnetic trip settings for the specific motor— specify motor horsepower, voltage, frequency, full-load current and code letter or locked rotor current.
3.
Refer to the tables and select an instantaneous-trip circuit breaker with an ampere rating recommended for the hp and voltage involved.
4.
Select an adjustable trip setting of at least 800%, not to exceed 1300%, of the motor full-load amperes (FLA) for other than Design E motors. For Design E motors, select an adjustable trip setting of at least 1100% not to exceed 1700% of FLA.
5.
The NEC 1300% maximum setting may be inadequate for instantaneous-trip circuit breakers to withstand current surges typical of the magnetization current of autotransformer type reduced voltage starters, or open transition wye-delta starters during transfer from “start” to “run,” constant hp multi-speed motors, and motors labeled “high efficiency.” Select thermal-magnetic circuit breakers from page 7-32 for those applications.
6.
Part-winding motors, per NEC 430.3, should have two circuit breakers selected from the above at not more than one half the allowable trip setting for the horsepower rating. The two circuit breakers should operate simultaneously as a disconnecting means per NEC 430.103.
7.
Based on NEC 430.52 and NEC Table 430.150. See
page 7-30 for a listing of Square D Adjustable Instantaneous-Trip Circuit Breakers.
Table 7.67:
GJL Adjustable Instantaneous-trip Circuit Breakers for Single Motor Circuit Protection
200 Vac
230 Vac
460 Vac
575 Vac
0.8
1
900%
1.1
800%
1.4
600%
1
1.8
500%
2
500%
2.1
400%
2.3
400%
2.6
300%
2.7
300%
2.8
300%
3.2
700%
3.4
600%
3.6
600%
3.9
500%
4.1
500%
4.8
400%
5.2
400%
6
400%
6.1
700%
6.8
700%
7.6
600%
7.8
600%