Page 3-10
click here to download PDF version
Download PDF
Square D > On-line Catalog > Products > Safety Switches > Heavy Duty Safety Switches: Accessories

navigation start Table of Contents Previous Next Index end navigtion
Square D


Digest 174 Quick Page Locator
Enter a page number from our paper catalog to go directly to that page in our online catalog.
Example: 5 - 3

Section - Page
-

Heavy Duty Safety Switches

 

Accessories

Class 3110

Neutral Assemblies—Field-Installable Neutral Assemblies For Fusible and Non-Fusible 240 and 600 Volt Safety Switches
Switch Rating
(A)
Standard
Neutral Kit
Cat. No.
Terminal Data
AWG/kcmil
Optional Copper Only
Neutral Kit Cat. No.
Terminal Data
AWG/kcmil
F1, F5–F6
 (3) 2 Max. Al/Cu
 (3) 6 Max. Cu
F1–F3,
F5–F6 (600 V)
 (2) 1/0 Max. Al/Cu
 (2) 1/0 Max. Cu
 (2) 2 Max. Al/Cu
 (2) 6 Max. Cu
F4,
F5–F6 (240 V)
 (3) 2 Max. Al/Cu
 (3) 6 Max. Cu
F2–F6
 (2) 1/0 Max. Al/Cu
 (2) 1/0 Max. Cu
 (2) 6 Max. Al/Cu
 (2) 6 Max. Cu
F5–F6
 (2) 250 Max. Al/Cu
 (1) 1/0 Max. Al/Cu
 (2) 250 Max. Cu
 (1) 1/0 Max. Cu
E1–E4
 (4) 750 Max. Al/Cu
 (1) 300 Max. Al/Cu
 (2) 600 Max. Cu
 (2) 350 Max. Cu
 (1) 250 Max. Cu
E2–E4
 (6) 750 Max. Al/Cu
 (2) 350 Max. Al/Cu
E2–E4
 (8) 750 Max. Al/Cu
 (2) 350 Max. Al/Cu
a
The following series -F5–F6 devices use SN0610(C): H-361-2, H-361-2RB, H-361-2A and H-361-2AWK.
b
For 200% neutral, order (2) neutral kits and (1) SN20NI neutral jumper kit. Price $18.40. (2) 350 Max. Al/Cu.

Equipment Grounding Kits

Equipment grounding kits are field-installable and UL Listed in 30–1200 A heavy duty switches. For factory installation of equipment grounding kit, add suffix GL to standard Cat. No. (Example: H361GL).
Price = Switch + Kit Price.
*
Kits are factory-installed standard in 30–200 A series F NEMA 4-4X-5 (stainless) and 12, and in all NEMA 30–200 A Series F 4–6P switches.
Equipment Grounding Kits—Field- or Factory-Installable Equipment Grounding Kits–240 and 600 V
Series Number
(See pages 3-12, 3-13)
Standard
Cat. No.
Terminal Data
AWG/kcmil
Terminal Data
AWG/kcmil
F1, F5–F7
 (2) 12 Cu or (2) 10 Al or (1) 4 Max. Al/Cu
F1–F3d,
F5–F7 (600 V)
 (2) 2/0 Max. Al/Cu
F4,
F5–F6 (240 V)
 (2) 12 Cu or (2) 10 Al or (1) 4 Max. Al/Cu
F2–F7
 (2) 2/0 Max. Al/Cu
F5–F7
 (2) 2/0 Max. Al/Cu
E2–E4
 (2) 2/0 Max. Al/Cu
E2–E4
 (4) 350 Max. Al/Cu
E2–E4
 (8) 350 Max. Al/Cu
c
The following series -F5–F6 devices use GTK0610(C): H-361-2 and H-361-2RB
Table 3.26:

Special Paint

UL Listed heavy duty switches are available painted with special safety colors. Special colors available include: safety red, safety orange, safety yellow, safety green, safety blue, safety purple, black and white.
A minimum quantity of 10 is required. To order, add suffix SP to standard Cat. No. Specify color on order.

Phenolic Legend Plate

Available engraved and mounted on all heavy duty safety switches, except NEMA 7 and 9. Legend engraved in 1/4 in. high white letters on black background. Customer must provide legend. UL Listed.
Discount Schedule

navigation start Table of Contents Previous Next Index end navigtion


Release Date: 03/31/2007
Modification Date: 1/17/2008