225–1600 A Main Lugs Terminal Box (Tenant Circuit Breakers used as Service Disconnects—6 maximum)
|
QO (225 A, 2P, 40–125 A) d
|
QB (225 A, 2P or 3P, 70–225 A)
|
|
|
QO-VH (125 A, 2P, 40–125 A )
|
QO-VH (225 A, 2P, 40–60 A) d
|
|
|
QD (225 A, 2P or 3P, 70–225 A)
|
|
|
QOH (125 A, 2P, 40–125 A)
|
QOH (225 A, 2P, 40–60 A) d
|
|
|
QG (225 A, 2P or 3P, 70–225 A)
|
|
|
QJ (225 A, 2P or 3P, 70–225 A) c
|
DJM (400 A, 2P or 3P, 160–400 A) ec
|
|
|
EZ Meter-Pak—Main Lugs Terminal Box Applications Protected By Remote Main—See Figure 2
|
|
|
|
225–1600 A Main Lugs Terminal Box Must be protected by an upstream disconnecting means rated 10 k AIR minimum
|
QO (225 A, 2P, 40–125 A) d
|
QB (225 A 2P or 3P, 70–225 A)
|
DJM (400 A, 2P or 3P 160–400 A) e
|
|
|
QO-VH (125 A, 2P, 40–125 A)
|
225–1600 A Main Lugs Terminal Box must be protected by an upstream disconnecting means rated 22 k AIR minimum
|
QO-VH (225 A, 2P, 40–60 A) d
|
DJM (400 A, 2P or 3P, 160–400 A) e
|
|
|
QD (225 A 2P or 3P, 70–225 A)
|
225–1600 A Main Lugs Terminal Box must be protected by an upstream disconnecting means rated 25 k AIR minimum
|
DJM (400 A, 2P or 3P, 160–400 A) e
|
|
|
QOH (125 A, 2P, 40–125 A)
|
225–1600 A Main Lugs Terminal Box must be protected by an upstream disconnecting means rated 42 k AIR minimum
|
QOH (225 A, 2P, 40–60 A) d
|
DJM (400 A, 2P or 3P, 160–400 A) e
|
QO-VH (125 A, 2P, 40–125 A)
|
225–1600 A Main Lugs Terminal Box must be protected by a Square D circuit breaker Type LA (400 A max.) or MA (1000 A max.) Rated 42 k AIR minimum
|
QO-VH (225 A, 2P, 40–60 A) d
|
QD (225 A 2P or 3P, 70–225 A)
|
|
|
QG (225 A 2P or 3P, 70–225 A)
|
225–1600 A Main Lugs Terminal Box must be protected by an upstream disconnecting means rated 65 k AIR minimum
|
DJM (400 A, 2P or 3P, 160–400 A) e
|
QO-VH (125 A, 2P, 40–125 A)
|
225–1600 A Main Lugs Terminal Box must be protected by a Square D circuit breaker Type LH (400 A max.), MH (1000 A max.) or PA (1600 A max.) rated 65 k AIR minimum
|
QO-VH (225 A, 2P, 40–60 A) d
|
QD (225 A 2P or 3P, 70–225 A)
|
QD (225 A 2P or 3P, 70–225 A)
|
225–1600 A Main Lugs Terminal Box must be protected by a Square D circuit breaker Type MG (800 A max.), PG (1200 A max.) or RG (1600 A max.) rated 65 k AIR minimum
|
|
|
QJ (225 A 2P or 3P, 70–225 A ) c
|
225–1600 A Main Lugs Terminal Box must be protected by an upstream disconnecting means rated 100 k AIR minimum
|
DJM (400 A 2P or 3P, 160–400 A) ec
|
QO-VH (125 A, 2P, 40–125 A)
|
|
QO-VH (225 A, 2P, 40–60 A) d
|
QD (225 A 2P only, 70–225 A)
|
Must be protected by an upstream disconnection means with Class J (600 A max.), Class L (1200 A max.), Class R (600 A max.), Class T (300 Vac, 1200 A max.) or Class T (600 Vac, 800 A maximum) fuses. Or be protected by a Square D circuit breaker Type MJ (800 A max.), PJ (1200 A max.), PH (1600 A max.) or RJ (1600 A max.) rated 100 k AIR minimum.
|
QD (225 A 3P only, 70–225 A) c
|
|
|
|
|
|
|
400–1600 A EZM Main Device with Type LH (400 A Max.), MH (1000 A max.) or PA (1600 A max.) circuit breaker.
|
QO (225 A, 2P, 40–125 A) d
|
QB (225 A 2P or 3P, 70–225 A)
|
|
|
QO-VH (125 A, 2P, 40–125 A)
|
QO-VH (225 A, 2P, 40–60 A) d
|
QD (225 A 2P or 3P, 70–225 A)
|
DJM (400 A, 2P or 3P, 160–400 A) e
|
|
|
|
1000–1200 A Main Device with catalog number suffix "CBU" supplied with Type MHF circuit breaker.
|
|
|
QO-VH (125 A, 2P, 40–125 A)
|
QO-VH (225 A, 2P, 40–60 A) d
|
QD (225 A 2P only, 70–225 A)
|
QD (225 A 3P only, 70–225 A) c
|
DJM (400 A, 2P or 3P, 160–400 A) ec
|
QD (225 A 2P only, 70–225 A)
|
|
QD (225 A 3P only, 70–225 A) c
|
DJM (400 A 2P or 3P, 160–400 A) ec
|
|
|
|
|
|
400–800 A EZM Main Device (1Ø or 3Ø) with Class T (300 Vac) fuses installed. 1200 A EZM Main Device (1Ø only) with Class T (300 Vac) fuses installed.
|
QO (225 A, 2P, 40–125 A) d
|
QB (225 A 2P or 3P, 70–225 A)
|
|
|
QO-VH (125 A, 2P, 40–125 A)
|
|
QO-VH (225 A, 2P, 40–60 A) d
|
|
|
DJM (400 A, 2P, 160–400 A) e
|
|
|
|
|
QO-VH (125 A, 2P, 40–125 A)
|
400–800 A EZM Main Device (1Ø or 3Ø) with Class T (300 Vac) fuses installed.
|
QO-VH (225 A, 2P, 40–60 A) d
|
QD (225 A 2P, only, 70–225 A)
|
QD (225 A 3P only, 70–225 A) c
|
DJM (400 A, 2P or 3P, 160–400 A) ec
|
|
|