EZ Meter-Pak® Meter Centers

Selection Information

Class 4141

Select meter center configuration, main lugs only (Six Disconnect Rule), or remote main, main circuit breaker, or main fusible switch.
Turn to appropriate selection/pricing pages to determine catalog numbers for main device, branch units, and tenant circuit breakers to complete meter center.
Table 2.12:
UL Listed Meter Center Short Circuit Current Ratings (SCCR) Tenant breakers of same frame size having higher AIR values may replace tenant breakers as listed in tables below and maintain the series rating.
Short Circuit
Current Rating
(240 Vac
Maximum)ab
EZM Branch Unit Tenant Circuit Breaker
Types Available (Branch Unit Amperes max.,
Number of Poles, Tenant Circuit Breaker
Amperes Rating Range)
EZM Main Device with Integral Mounted Main,
Remote Mounted Main or without an Upstream Mounted Main
(Six Disconnect Rule)
10 kA
QO (125 A, 2P, 40–125 A)
225–1600 A Main Lugs Terminal Box
(Tenant Circuit Breakers used as Service Disconnects—6 maximum)
QO (225 A, 2P, 40–125 A)d
QB (225 A, 2P or 3P, 70–225 A)
22 kA
QO-VH (125 A, 2P, 40–125 A )
QO-VH (225 A, 2P, 40–60 A)d
25 kA
QD (225 A, 2P or 3P, 70–225 A)
42 kA
QOH (125 A, 2P, 40–125 A)
QOH (225 A, 2P, 40–60 A)d
65 kA
QG (225 A, 2P or 3P, 70–225 A)
QJ (225 A, 2P or 3P, 70–225 A) c
DJM (400 A, 2P or 3P, 160–400 A)ec
EZ Meter-Pak—Main Lugs Terminal Box Applications Protected By Remote Main—See Figure 2
10 kA
QO (125 A, 2P, 40–125 A)
225–1600 A Main Lugs Terminal Box Must be protected by an upstream disconnecting means rated 10 k AIR minimum
QO (225 A, 2P, 40–125 A)d
QB (225 A 2P or 3P, 70–225 A)
DJM (400 A, 2P or 3P 160–400 A)e
22 kA
QO-VH (125 A, 2P, 40–125 A)
225–1600 A Main Lugs Terminal Box must be protected by an upstream disconnecting means rated 22 k AIR minimum
QO-VH (225 A, 2P, 40–60 A)d
DJM (400 A, 2P or 3P, 160–400 A)e
25 kA
QD (225 A 2P or 3P, 70–225 A)
225–1600 A Main Lugs Terminal Box must be protected by an upstream disconnecting means rated 25 k AIR minimum
DJM (400 A, 2P or 3P, 160–400 A)e
42 kA
QOH (125 A, 2P, 40–125 A)
225–1600 A Main Lugs Terminal Box must be protected by an upstream disconnecting means rated 42 k AIR minimum
QOH (225 A, 2P, 40–60 A)d
DJM (400 A, 2P or 3P, 160–400 A)e
QO-VH (125 A, 2P, 40–125 A)
225–1600 A Main Lugs Terminal Box must be protected by a Square D circuit breaker
Type LA (400 A max.) or MA (1000 A max.) Rated 42 k AIR minimum
QO-VH (225 A, 2P, 40–60 A)d
QD (225 A 2P or 3P, 70–225 A)
65 kA
QG (225 A 2P or 3P, 70–225 A)
225–1600 A Main Lugs Terminal Box must be protected by an upstream disconnecting means rated 65 k AIR minimum
DJM (400 A, 2P or 3P, 160–400 A)e
QO-VH (125 A, 2P, 40–125 A)
225–1600 A Main Lugs Terminal Box must be protected by a Square D circuit breaker Type LH (400 A max.), MH (1000 A max.) or PA (1600 A max.) rated 65 k AIR minimum
QO-VH (225 A, 2P, 40–60 A)d
QD (225 A 2P or 3P, 70–225 A)
QD (225 A 2P or 3P, 70–225 A)
225–1600 A Main Lugs Terminal Box must be protected by a Square D circuit breaker Type MG (800 A max.), PG (1200 A max.) or RG (1600 A max.) rated 65 k AIR minimum
QJ (225 A 2P or 3P, 70–225 A )c
225–1600 A Main Lugs Terminal Box must be protected by an upstream disconnecting means rated 100 k AIR minimum
DJM (400 A 2P or 3P, 160–400 A)ec
QO-VH (125 A, 2P, 40–125 A)
QO-VH (225 A, 2P, 40–60 A)d
QD (225 A 2P only, 70–225 A)
Must be protected by an upstream disconnection means with Class J (600 A max.), Class L (1200 A max.), Class R (600 A max.), Class T (300 Vac, 1200 A max.) or Class T (600 Vac, 800 A maximum) fuses. Or be protected by a Square D circuit breaker Type MJ (800 A max.), PJ (1200 A max.), PH (1600 A max.) or RJ (1600 A max.) rated 100 k AIR minimum.
QD (225 A 3P only, 70–225 A)c
EZ Meter-Pak—Main Circuit Breaker Applications—See Figure 3
QO (125 A, 2P, 40–125 A)
400–1600 A EZM Main Device with Type LH (400 A Max.), MH (1000 A max.) or PA (1600 A max.) circuit breaker.
QO (225 A, 2P, 40–125 A)d
QB (225 A 2P or 3P, 70–225 A)
QO-VH (125 A, 2P, 40–125 A)
QO-VH (225 A, 2P, 40–60 A)d
QD (225 A 2P or 3P, 70–225 A)
DJM (400 A, 2P or 3P, 160–400 A)e
QD (225 A, 3P, 70–225 A)
1000–1200 A Main Device with catalog number suffix "CBU" supplied with
Type MHF circuit breaker.
QO-VH (125 A, 2P, 40–125 A)
QO-VH (225 A, 2P, 40–60 A)d
QD (225 A 2P only, 70–225 A)
QD (225 A 3P only, 70–225 A)c
DJM (400 A, 2P or 3P, 160–400 A)ec
QD (225 A 2P only, 70–225 A)
QD (225 A 3P only, 70–225 A)c
DJM (400 A 2P or 3P, 160–400 A)ec
EZ Meter-Pak—Main Fusible Switch Applications—See Figure 3
QO (125 A, 2P, 40–125 A)
400–800 A EZM Main Device (1Ø or 3Ø) with Class T (300 Vac) fuses installed. 1200 A EZM Main Device (1Ø only) with Class T (300 Vac) fuses installed.
QO (225 A, 2P, 40–125 A)d
QB (225 A 2P or 3P, 70–225 A)
QO-VH (125 A, 2P, 40–125 A)
QO-VH (225 A, 2P, 40–60 A)d
DJM (400 A, 2P, 160–400 A)e
QD (225 A 2P, 70–225 A)
QO-VH (125 A, 2P, 40–125 A)
400–800 A EZM Main Device (1Ø or 3Ø) with Class T (300 Vac) fuses installed.
QO-VH (225 A, 2P, 40–60 A)d
QD (225 A 2P, only, 70–225 A)
QD (225 A 3P only, 70–225 A)c
DJM (400 A, 2P or 3P, 160–400 A)ec