Schneider Electric Brands
Page 21-33
click here to download PDF version
Download PDF

 Square D > On-line Catalog > Products > Relays and Timers > Liquid Level Relays
Search     
Table of Contents Previous Page Next Page Product Index


Liquid Level Relays

RM4L


Liquid Level Control Relays
Time Delay
Sensitivity Scale
Width
IN
Width
mm
Output Relay
Voltage
50/60 Hz
Catalog Number
Price
None  
5–100 kΩ  
0.87  
22.5  
1 C/O  
SPDT  
24 Vac  
$176.  
110–130 Vac  
176.  
220–240 Vac  
176.  
380–415 Vac  
176.  
Adjustable  
0.1–10 s  
0.25–5 kΩ  
2.5 –50 kΩ  
25–500 kΩ  
0.87  
22.5  
2 C/O  
DPDT  
24–240 Vac or Vdc  
290.  
24 Vac  
248.  
110–130 Vac  
248.  
220–240 Vac  
248.  
380–415 Vac  
248.  


Liquid Level Control Probe
Type of Installation
Maximum Operating Temperature
Catalog Number
Price
Suspended by cable
212° F (100° C)  
$65.  


Power Supply Circuit Specifications
Type of Relay
50/60 Hz
RM4LG01
RM4LA32
Rated Supply
Voltage (Un)
50/60 Hz
Vac
24 Vac  
110–130 Vac  
220–240 Vac  
380–415 Vac  
24–240 Vac  
24 Vac  
110–130 Vac  
220–240 Vac  
380–415 Vac  
Vdc
. . .  
. . .  
. . .  
. . .  
24–240 Vdc  
. . .  
. . .  
. . .  
. . .  
Average
Consumption at Un
Vac
1.9 VA  
2.6 VA  
2.4 VA  
2.9 VA  
2.7 VA  
3.1 VA  
2.7 VA  
2.6 VA  
3.4 VA  
Vdc
. . .  
. . .  
. . .  
. . .  
2.4 W  
. . .  
. . .  
. . .  
. . .  


Output Relay and Operating Specifications
Number of SPDT (C/O) Contacts
1 C/O SPDT
2 C/O DPDT
Output Relay State
Can be configured by switch: empty fill


Electrode Circuit Specifications a
Sensitivity Scale
5-100 (adjustable) kΩ
0.25-5 kΩ
2.5-50 kΩ
25-500 kΩ
Maximum AC Electrode Voltage (peak to peak)
24 V
24 V
Maximum Current in the
Electrodes
1 mA
1 mA
1 mA
1 mA
Maximum Cable Capacity
10 nF
200 nF
25 nF
4 nF
Maximum Cable Length
330 ft (100 m)
3300 ft (1000 m)
330 ft (100 m)
66 ft (20 m)

a The electrodes may also be incorporated in the probes. The probes are normally designed for fixing to a tank by means of a bracket with a seal (closed tanks) or suspended by their own electrical connecting cable (boreholes, etc.).


Approvals/Standards
Conforming to Standards
IEC 60255-6 EN 60255-6
Temperature Ratings
Storage
-40° F to 185° F (-40° C to 85° C)
Operational
-4° F to 149° F (-20° C to 65° C)
Supply Voltage Range
-15 to +10% rated of supply voltage

For additional information, reference Catalog #8430CT0001R6/02.



I11

          

Discount
Schedule

9/8/03 © 2005 Schneider Electric
All Rights Reserved
 
Table of Contents Previous Page Next Page Product Index

Square D US
Telemecanique US
Merlin Gerin US