Voltage Measurement Relays

RM4


Power Supply Circuit Specifications
Type of Relay
RM4UA0
RM4UA3
Rated Supply
Voltage (Un)
Vac 50/60 Hz
24 Vac  
110–130 Vac  
220–240 Vac  
24–240 Vac  
110–130 Vac  
220–240 Vac  
380–415 Vac  
Vdc
. . .  
. . .  
. . .  
24–240 Vdc  
. . .  
. . .  
. . .  
Average
Consumption at Un
Vac
2 VA  
1.9–3.3 VA  
2.7–3.5 VA  
1.5–3.3 VA  
1.9–3.3 VA  
2.7–3.4 VA  
2.7–3 VA  
Vdc
. . .  
. . .  
. . .  
1.2 W  
. . .  
. . .  
. . .  


Output Relay and Operating Specifications
Type of Relay
RM4UA0
RM4UA3
Number of C/O Contacts SPDT
 
1
2
Output Relay State
Energized when:
voltage measured > threshold setting
Energized when:
voltage measured > threshold setting (">" function)
voltage measured < threshold setting ("<" function)
Setting Accuracy of the Switching Threshold
As % of the full scale value: ± 5 %
Switching Threshold Drift
0.06 % per degree centigrade, depending on the permissible ambient temperature
0.5 %, within the supply voltage range (0.85–1.1 Un)
Hysteresis (adjustable)
5-30 % of the voltage threshold setting
Setting Accuracy of the Time Delay
As % of the full scale value: ± 10 %
Time Delay Drift
. . .
0.5 %, within the supply voltage range (0.85–1.1 Un)
0.07 % per degree centigrade, depending on temperature
Measuring Cycle
80 ms
Approvals/Standards
Conforming to Standards
IEC 60255-6 EN 60255-6
Temperature Ratings
Storage
-40° F to 185° F (-40° C to 85° C)
Operational
-4° F to 149° F (-20° C to 65° C)
Supply Voltage Range
-15 to +10% rated of supply voltage


Measuring Input Specifications
Internal Input Resistance and Permissible Overload Depending on the Current Measurement Ranges
Type of Relay
RM4UA1
RM4UA2
RM4UA3
Measurement Range 50-60 Hz Vac and Vdc
0.05–0.5 V
0.3–3 V
0.5–5 V
1–10 V
5–50 V
10–100 V
30–300 V
50–500 V
Internal Input Resistance Ri
6.6 kΩ
43 kΩ
71 kΩ
23 kΩ
112 kΩ
225 kΩ
668 kΩ
1111 kΩ
Permissible Continuous Overload
20 V
60 V
80 V
90 V
150 V
300 V
400 V
550 V
Permissible Non Repetitive Overload for t 1 s
25 V
80 V
100 V
100 V
200 V
400 V
500 V
550 V


Voltage Measurement Relays: Overvoltage Detection
Time Delay
Voltage to be Measured Depending on Connection VAC or VDC
Width
IN
Width
mm
Output Relay
Supply Voltage
50/60 Hz
Catalog Number
Price
None
0.05–0.5 V
0.3–3 V
0.5–5 V
0.89  
22.5  
1 C/O SPDT  
24 Vac
$279.  
110–130 Vac
279.  
220–240 Vac
279.  
1–10 V
5–50 V
10–100 V
0.89  
22.5  
1 C/O SPDT  
24 Vac
279.  
110–130 Vac
279.  
220–240 Vac
279.  
30–300 V
50–500 V
0.89  
22.5  
1 C/O SPDT  
24 Vac
279.  
110–130 Vac
279.  
220–240 Vac
279.  


Voltage Measurement Relays: Overvoltage or Undervoltage Detection
Adjustable Time Delay
Voltage to be Measured Depending on Connection VAC or VDC
Width
IN
Width
mm
Output Relay
Supply Voltage
50/60 Hz
Catalog Number
Price
0.05–30 s
0.05–0.5 V
0.3–3 V
0.5–5 V
0.89  
22.5  
2 C/O DPDT  
24–240 Vac/dc
$362.  
110–130 Vac
311.  
220–240 Vac
311.  
380–415 Vac
311.  
1–10 V
5–50 V
10–100 V
1.77  
45  
2 C/O DPDT  
24–240 Vac/dc
362.  
110–130 Vac
311.  
220–240 Vac
311.  
380–415 Vac
311.  
30–300 V
50–500 v
1.77  
45  
2 C/O DPDT  
24–240 Vac/dc
362.  
110–130 Vac
311.  
220–240 Vac
311.  
380–415 Vac
311.  

For additional information, reference Catalog #8430CT0001R6/02.



I11

          

Discount
Schedule

9/8/03 © 2005 Schneider Electric
All Rights Reserved
 
Table of Contents Previous Page Next Page Product Index