AC
|
DC
|
||||
|---|---|---|---|---|---|
Type
|
AC Volts |
Resistive 75% PF Continuous Amperes |
Hp
|
DC Volts |
Resistive Amperes |
120
| 10
| 28
|
10
|
||
240
| 10 b
| ||||
120
| 15 c
| 28
|
10
|
||
240
| |||||
KL
|
120
| 10
| 28
|
10
|
|
240
| 10
| ||||
Type
|
Comments
|
|
|---|---|---|
Typical Pick-Up Time
|
KP
| AC coil: approximately 12 ms
DC coil: approximately 18 ms
|
KF, KU
| AC coil: approximately 8 ms
DC coil: approximately 11 ms
| |
KL
| approximately 25 ms
| |
Typical Drop-Out Time
|
KP
| AC coil: approximately 12 ms
DC coil: approximately 7 ms
|
KF, KU
| AC coil: approximately 8 ms
DC coil: approximately 7 ms
| |
KL
| approximately 25 ms
| |
Operating Temperature Range |
KF, KP, KU
| AC: 2 pole: -40° C to +55° C (-40° F to +131° F)
3 pole: -40° C to +45° C (-40° F to +113° F)
DC: -40° C to +70° C (-40° F to +158° F)
|
KL
| AC/DC: -45° C to +70° C (-49° F to +158° F)
| |
Contacts |
||
Configuration
| 2PDT or 3PDT (2 or 3 Form C)
|
|
Ratings
| See contact ratings table above.
|
|
Material
| KF, KU, and KL—Silver cadmium oxide
KP—Silver nickel
|
|
Coils |
||
Duty
| Continuous rated coils
|
|
Available Voltages
| See Stocked Relays page 21-15.
|
|
Operate
| AC: +10, -15% of Nominal Voltage at 25° C (77° F)
DC: +10, -25% of Nominal Voltage at 25° C (77° F)
|
|
Typical Burden
|
Types KP, KU, KF
| AC: 3.6 VA inrush, 2.5 VA sealed
DC: 1.5 watts standard, 3 watts maximum
|
Type KL
| AC: 2.0 VA latch, 0.8 VA unlatch
DC: 1.2 watts
| |
Terminals: Solder/plug-in
UL/CSA:
For additional information, reference Catalog #8501CT0301.
| 9/8/03 | © 2005 Schneider Electric All Rights Reserved |
![]() |
||||||
|
|