Straight-through wiring |
![]() |
Plug-in contact cartridges for easy contact conversion and replacement |
![]() |
Contact conversion without removing terminal screws or wires |
![]() |
Self-lifting pressure wire connectors |
![]() |
Replaceable coil |
Normally Open Convertible
Instantaneous Contacts
|
Control Relay a
|
|
|---|---|---|
Type
|
Price
|
|
0
2
3
4
6
8
10
12
| XO00d
XO20d
XO30d
XO40d
XO60d
XO80d
XO1000d
XO1200d
| $ 77.
114.
134.
152.
191.
228.
266.
305.
|
![]() |
20 ampere contact rating due to use of master contact cartridges. c |
![]() |
Provisions for standard cartridges to be used in contact cavities not occupied by master cartridges in 2-8 pole AC relay. |
Number of N.O. 20 Ampere Convertible Contacts |
Open Typeb
|
|
|---|---|---|
Type
|
Price
|
|
2
4
6
| XMO20d
XMO40d
XMO60d
| $171.
266.
362.
|
![]() |
Easily convertible On Delay or Off Delay |
![]() |
Two adjustable timing ranges |
![]() |
Repeat accuracy well above ±10% |
![]() |
Convertible 1 N.O. and 1 N.C. timed contacts |
![]() |
Large knob for easy adjustment of time delay |
![]() |
Off Delay mode times out even after loss of power. |
Timing
Mode
|
Normally Open Convertible Instantaneous Contacts |
Timed Convertible Contacts |
Timing Relay
|
Price
|
||
|---|---|---|---|---|---|---|
0.2–60 sec.
|
5–180 sec.
|
|||||
N.O.
|
N.C.
|
Type
|
Type
|
|||
On Delay
| 0
2
4
| 1
1
1
| 1
1
1
| XO00XTE1d
XO20XTE1d
XO40XTE1d
| XO00XTE2d
XO20XTE2d
XO40XTE2d
| $342.
380.
419.
|
Off Delay
| 0
2
4
| 1
1
1
| 1
1
1
| XO00XTD1d
XO20XTD1d
XO40XTD1d
| XO00XTD2d
XO20XTD2d
XO40XTD2d
| 342.
380.
419.
|
![]() |
Mechanical latch holds all contacts switched even after removal of power from replaceable latching coil. |
![]() |
Provides sequence memory in the event of power loss. Ideal for press control, process control and punch presses. |
![]() |
Replaceable unlatch coil to switch contacts back to original state. |
![]() |
Continuously rated unlatch coil (no coil clearing contacts required). |
Normally Open Convertible
Instantaneous Contacts
|
Latching Relay
|
|
|---|---|---|
Type
|
Price
|
|
2
3
4
6
8
| XO20XLd
XO30XLd
XO40XLd
XO60XLd
XO80XLd
| $248.
266.
285.
323.
362.
|
Type of Cartridge |
Volts
|
Inductive
35% Power Factor
|
Resistive
75% PowerFactor
|
|||||
|---|---|---|---|---|---|---|---|---|
NEMA
Rating
|
Make
|
Break
|
Continuous
Amperes
|
Make, Break and Continuous Amperes |
||||
A
|
VA
|
A
|
VA
|
|||||
Standard
| 120
240
480
600
|
A600
|
60
30
15
12
|
7200
|
6
3
1.5
1.2
|
720
|
10
|
10
|
Overlapping
| ||||||||
Masterc
| . . .
| A600
| Same as standard cartridge above except substitute
20 ampere for the continuous ampere rating
|
|||||
Logic Reed
| . . .
| . . .
| 150 Vac, 150 mA, 8 W Maximum
|
|||||
Device
|
Pick-Up
|
Drop-Out
|
|---|---|---|
AC Relay
| 15
| 16
|
AC Latching Relay
| 15
| 13
|
AC Voltages - Hz
|
Code
|
|---|---|
12–60
24–60
24–50
48–60
48–50
120–60/110–50
208–60
240–60/220–50
277–60
480–60/440–50
600–60/550–50
| V11
V01
V12
V18
V16
V02
V08
V03
V04
V06
V07
|
No.
of
Poles
|
"A"
Dim.
|
Shipping
Weight
Lbs.
|
|
|---|---|---|---|
IN
|
mm
|
||
0–4
| 3.95
| 100
| 2.0
|
6–8
| 5.16
| 131
| 2.3
|
10–12
| 6.36
| 162
| 2.7
|
No.
of
Poles
|
"A"
Dim.
|
Shipping
Weight
Lbs.
|
|
|---|---|---|---|
IN
|
mm
|
||
2–4
| 6.54
| 166
| 2.8
|
6–8
| 7.74
| 197
| 3.1
|
For Replacement coils page 21-7
For additional information, reference Catalog #8501CT9601.
| 8/4/04 | © 2005 Schneider Electric All Rights Reserved |
![]() |
||||||
|
|