Schneider Electric Brands
Page 16-50
click here to download PDF version
Download PDF

Search     
Table of Contents Previous Page Next Page Product Index


TeSys GV2 and GV3

Manual Starter and Protector

The GV2 and GV3 devices are 3-pole, horsepower-rated manual starters. They include a manual disconnect, Class 10 ambient-compensated, bi-metallic thermal overload relay, and an instantaneous magnetic trip mechanism in one compact unit.

Either starter can be used alone for local, manual control of a single motor or can be wired in front of a contactor to provide a complete, remotely operated motor control circuit. The GV2 and GV3 are particularly effective when multiple motor circuits are to be housed in one panel.

The GV2 and GV3 devices are UL Listed for group installations for motors with individual full-load currents up to 63 A. If each motor in a grouping is controlled by a GV2 or GV3 device, only one branch circuit protective device (circuit breaker or fusing) is necessary for the entire group. The table below specifies the maximum allowable size of the branch protector for each manual starter, in accordance with National Electrical Code Article 430-53.

The GV2P is listed and approved for UL 508 Type E self-protected starter applications when used with incoming line insulator GV2GH7.

The interrupting rating for group installations is 10 kA at 480 V for the GV2M and 50 kA at 480 V for both the GV2P and GV3M devices. The instantaneous trip is set at 13 times the thermal trip setting and is not adjustable.

The GV2M and the GV3M manual starters feature pushbutton control to indicate the ON or OFF state of the device. The GV2P features a rotary handle which indicates the ON or OFF state and also whether the unit has been tripped by overload, short-circuit, undervoltage, or shunt trip. All devices are now available with spring terminal clamps. Add "3" to the end of the catalog number.

How to Order

To order the basic motor starter, select the model number (GV2ME, GV2P, or GV3ME) with the appropriate thermal setting from the table below. The thermal trip range and setting should be determined from the motor nameplate full-load current.



Thermal
Setting
(A)
Maximum Horsepower Ratings
Group Motor
Applications
GV2/3M pushbutton
GV2P rotary handle
115 V
hp
230 V
hp
200 V
hp
230 V
hp
460 V
hp
575 V
hp
Max. Fuse or Circuit Breaker
Catalog
Number
Price
Catalog
Number
Price
0.11-0.16  
. . .  
. . .  
. . .  
. . .  
. . .  
. . .  
1200 A  
$106.00  
$141.00  
0.16-0.25  
. . .  
. . .  
. . .  
. . .  
. . .  
. . .  
1200 A  
106.00  
141.00  
0.25-0.40  
. . .  
. . .  
. . .  
. . .  
. . .  
. . .  
1200 A  
106.00  
141.00  
0.40-0.63  
. . .  
. . .  
. . .  
. . .  
. . .  
. . .  
1200 A  
120.00  
155.00  
0.63-1  
. . .  
. . .  
. . .  
. . .  
1/2  
1/2  
1200 A  
120.00  
155.00  
1-1.6  
. . .  
1/10  
. . .  
. . .  
3/4  
1  
1200 A  
120.00  
155.00  
1.6-2.5  
. . .  
1/6  
1/2  
1/2  
1  
11/2  
1200 A  
120.00  
155.00  
2.5-4  
1/8  
1/3  
3/4  
1  
2  
3  
1200 A  
120.00  
155.00  
4-6.3  
1/4  
1/2  
11/2  
11/2  
3  
5  
1200 A  
120.00  
155.00  
6-10  
1/2  
11/2  
2  
3  
5  
71/2  
1200 A  
120.00  
155.00  
9-14  
3/4  
2  
3  
3  
10  
10  
1200 A  
149.00  
185.00  
13-18  
1  
3  
5  
5  
10  
15  
1200 A  
149.00  
185.00  
17-23  
11/2  
3  
5  
71/2  
15  
20  
1200 A  
149.00  
185.00  
20-25  
2  
3  
5  
71/2  
15  
20  
1200 A  
149.00  
185.00  
24-32  
2  
5  
10  
10  
20  
30  
1200 A  
149.00  
185.00  
1-1.6  
. . .  
1/10  
. . .  
. . .  
3/4  
1  
500 A  
269.00  
. . .  
. . .  
1.6-2.5  
. . .  
1/16  
1/2  
1/2  
1  
11/2  
500 A  
269.00  
. . .  
. . .  
2.5-4  
1/8  
1/3  
3/4  
1  
2  
3  
500 A  
269.00  
. . .  
. . .  
4-6  
1/4  
1/2  
11/2  
11/2  
3  
. . .  
500 A  
269.00  
. . .  
. . .  
6-10  
1/2  
11/2  
2  
3  
5  
71/2  
500 A  
269.00  
. . .  
. . .  
10-16  
1  
2  
3  
5  
10  
10  
500 A  
299.00  
. . .  
. . .  
16-25  
2  
3  
5  
71/2  
15  
20  
500 A  
299.00  
. . .  
. . .  
25-40  
3  
71/2  
10  
10  
25  
30  
500 A  
336.00  
. . .  
. . .  
40-63  
5  
10  
20  
20  
40  
60  
500 A  
336.00  
. . .  
. . .  

a For spring terminals add 3 to the catalog number, for example, GV2ME013. GV2ME32 is not available with spring terminals.

Specifications
Operating Positions:
Shock resistance—30 g (conforming to IEC 600 68-2-27)
Vibration resistance—5 g (5 to 150 Hz) (IEC 600 68-2-26)
Ambient temperature:
-40 to 176° F (-40 to +80° C) for storage
-4 to 140° F (-20 to +60° C) open operation
-4 to 104° F (-20 to +40°C) enclosed operation
Rated voltage—600 V
Rated thermal current—25 A (GV2), 63 A (GV3)
Interrupting current at 480 V:
 12 kA (GV2M), 50 kA (GV2P and GV3M)
Ambient temperature compensation:
-4 to 140°F (-20 to +60°C) open operation
-4 to 104°F (-20 to +40°C) enclosed operation
Mechanical life:
 GV2:
 GV3M06 to M25:
 GV3M40 to M63:

100,000 operations
100,000 operations
63,000 operations
Maximum operating life—25 operations per hour
Operating current of magnetic trip is approximately
13 times maximum thermal trip (non-adjustable setting)