Special Voltage, Shielded Isolation, Drive Isolation and Buck Boost Transformers Class 7400

Special Voltage Transformers—Shielded and Non-shielded

Square D offers special voltage transformers built to customer specifications. Many options such as lower sound level, copper windings, special frequency, etc. are available but not listed below. Contact your nearest Square D/Schneider Electric sales office for details.

All two-winding transformers are "isolating" or "insulating" because there is no electrical connection between the primary and secondary windings. Additionally, critical equipment might require an electrostatic shield be furnished between primary and secondary to attenuate some of the source line interference and common-mode noise.

Protection from transverse-mode transients is obtained by adding surge suppressors and filters to the shielded isolation transformer.

Single phase units are listed on page 12-2.

Electrostatic Shield is indicated by the letters IS at the end of the catalog number.


Three Phase 480 V Delta Primary
208Y/120 V Secondary 60 Hz with Electrostatic Shield, cULus Listed
kVA
Catalog
Numbera
Price
Stocked
Voltage Codes
Degree C
Temp. Rise
Weight
(Pounds) c
Enclosure
 9  
$ 2311.  
2–5%FCBN
115  
 235  
14C  
 15  
2878.  
6–2.5%2 + 4–
150  
 200  
17D  
 30  
3625.  
6–2.5%2 + 4–
150  
 250  
17D  
 45  
4360.  
6–2.5%2 + 4–
150  
 340  
18D  
 75  
6567.  
6–2.5%2 + 4–
150  
 500  
19D  
 112.5  
8550.  
6–2.5%2 + 4–
150  
 815  
21D  
 150  
10908.  
6–2.5%2 + 4–
150  
 800  
22D  
 225  
14609.  
6–2.5%2 + 4–
150  
1025  
24D  
 300  
19174.  
6–2.5%2 + 4–
150  
1450  
25D  
 500  
29327.  
4–2.5%2 + 2–
150  
2100  
30D  
208 V Delta Primary
208Y/120 V Secondary 60 Hz with Electrostatic Shield, cULus Listed
 9  
$ 2311.  
2–5%FCBN
115  
 235  
14C  
 15  
2878.  
2–5%FCBN
150  
 200  
17D  
 30  
3625.  
2–5%FCBN
150  
 250  
17D  
 45  
4360.  
2–5%FCBN
150  
 340  
18D  
 75  
6567.  
2–5%FCBN
150  
 500  
19D  
 112.5  
9190.  
2–5%FCBN
150  
 815  
21D  
 150  
10908.  
2–5%FCBN
150  
 800  
22D  
 225  
14609.  
2–5%FCBN
150  
1025  
24D  
 300  
19174.  
2–5%FCBN
150  
1450  
25D  
 500  
29327.  
2–5%FCBN
150  
2100  
30D  

Shielded Transformers with Filters—Three Phase

Additional attenuation of transverse (across-the-line) surges and transients is available with the addition of primary surge suppression and secondary filters. Surge suppression and filtering are indicated by the letters FIL at the end of the catalog number.


480 V Delta Primary 208Y/120 V Secondary 60 Hz with Electrostatic Shield, Surge Suppressors and Filter – cULus Listed
kVA
Catalog
Numbera
Price
Full Capacity
Taps
Degree C
Temp. Rise
Weight
(Pounds) c
Enclosure
 15  
$ 6202.  
6–2.5%2 + 4–
150  
 265  
19D  
 30  
6948.  
6–2.5%2 + 4–
150  
 295  
19D  
 45  
8425.  
6–2.5%2 + 4–
150  
 390  
19D  
 75  
10633.  
6–2.5%2 + 4–
150  
 610  
21D  
112.5  
13210.  
6–2.5%2 + 4–
150  
 840  
22D  
150  
15568.  
6–2.5%2 + 4–
150  
1100  
25D  
225  
19638.  
6–2.5%2 + 4–
150  
1400  
26D  
208 V Delta Primary 208Y/120 V Secondary 60 Hz with Electrostatic Shield, Surge Suppressors and Filter – cULus Listed
 15  
$ 6202.  
2–5% FCBN
150  
 265  
19D  
 30  
6948.  
2–5% FCBN
150  
 295  
19D  
 45  
8425.  
2–5% FCBN
150  
 390  
19D  
 75  
10633.  
2–5% FCBN
150  
 610  
21D  
112.5  
13210.  
2–5% FCBN
150  
 840  
22D  
150  
15568.  
2–5% FCBN
150  
1100  
25D  
225  
19638.  
2–5% FCBN
150  
1400  
26D  

FCBN = Full capacity below normal
Lugs: Furnished by customer.
Taps on transformers 225 kVA and larger may vary in 3% to 5% steps to obtain best design.

Product Data Bulletin 7400PD9202 describes technical details of shielded and filtered transformers.

Drive Isolation Transformers—Three Phase

Special design considerations must be made for the requirements of both adjustable frequency and dc motor drive power isolation. Allowance for high surge, harmonic and offset currents are taken into account in the design of Square D Company drive isolation transformers. Drive isolation transformers are not shielded isolation transformers, but act to lessen transient generation into the supply power and act as a buffer for SCR current surges. cULus Listed.


Three Phase  60 Hz  Class B (IEEE Standard 597-1983)
kVA
Catalog
Numbera
Price
Stock Voltage Codes
Degree C
Temp. Rise
Weight
(Pounds) c
Enclosure
 7.5  
7T( )HDIT
$ 2231.  
144, 145  
150  
 180  
17D  
 11  
11T( )HDIT
2649.  
144, 145  
150  
 180  
17D  
 15  
15T( )HDIT
2732.  
144, 145  
150  
 190  
17D  
 20  
20T( )HDIT
3275.  
144, 145  
150  
 210  
17D  
 27  
27T( )HDIT
3360.  
144, 145  
150  
 250  
17D  
 34  
34T( )HDIT
3696.  
144, 145  
150  
 295  
18D  
 40  
40T( )HDIT
4202.  
144, 145  
150  
 350  
18D  
 51  
51T( )HDIT
4913.  
144, 145  
150  
 445  
20D  
 63  
63T( )HDIT
5346.  
144, 145  
150  
 465  
20D  
 75  
75T( )HDIT
6249.  
144, 145  
150  
 550  
20D  
 93  
93T( )HDIT
8010.  
144, 145  
150  
 845  
22D  
 118  
118T( )HDIT
8922.  
145  
150  
 920  
22D  
 145  
145T( )HDIT
10004.  
145  
150  
1025  
22D  
 175  
175T( )HDIT
11546.  
145  
150  
1120  
25D  
 220  
220T( )HDIT
14112.  
145  
150  
1200  
25D  
 275  
275T( )HDIT
18858.  
145  
150  
1500  
25D  
 330  
330T( )HDIT
19844.  
145  
150  
1390  
25D  
 440  
440T( )HDIT
24325.  
None  
150  
2700  
30D  
 550  
550T( )HDIT
30222.  
None  
150  
3800  
30D  


Voltage Codes
Code
Primary
Secondary
Full Capacity Taps
142  
143  
144  
230 Delta  
230 Delta  
460 Delta  
230Y/132  
460Y/265  
230Y/132  
2–5%1 + 1–  
145  
146  
147  
460 Delta  
575 Delta  
575 Delta  
460Y/265  
230Y/132  
460Y/265  

To Complete Catalog Number:

1. Select the voltage required from chart.
2. Insert the voltage code number in place of the ( ) in the catalog number.

See Handout 7460HO9501 for additional information.

Single Phase—Buck and Boost Transformers

Buck and Boost transformers are isolating transformers that have 120 X 240 volt primaries and either 12/24 or 16/32 volt secondaries. When used as isolating transformers they carry the full load stated on the nameplate. By special interconnection of the windings, an auto-transformer is obtained. When used this way for bucking or boosting small voltage changes, the kVA load they carry is large compared to their physical size.

Note: When used to supply a 3-phase, 4-wire load, the source must be 3-phase, 4-wire.

Single Phase
UL/cULus Listed. Copper Windings.
kVA
120 x 240 V Primary
60 Hza
240 x 480 V
Primary 60 Hza
Degree C
Temp. Rise
Weightc
(Pounds)
Enclosure
b c
12/24 V
Secondary
16/32 V
Secondary
Price
24/48 V
Secondary
Price
 .05  
$ 103.  
$ 142.  
 55  
 4.2  
1A  
 .10  
123.  
172.  
 55  
 4.5  
2A  
 .15  
138.  
193.  
 55  
 6.2  
3A  
 .25  
164.  
230.  
80  
 10.5  
4A  
 .50  
210.  
294.  
80  
 13.8  
5A  
 .75  
276.  
387.  
115  
 15.5  
6A  
 1.0  
338.  
474.  
115  
 21.2  
7A  
 1.5  
415.  
581.  
115  
 30.1  
8A  
 2.0  
536.  
750.  
115  
 39.1  
9A  
 3.0  
740.  
1036.  
115  
 60  
d  

a Catalog Numbers shown in bold type are available from Distribution Center.
b For enclosure styles, see Dimensions Table, page 12-10.
c Not for construction. Contact your nearest Square D/Schneider Electric sales office for certified prints.
d Dimensions: 14.5" high x 8.6" wide x 6.5" deep.
Lugs: Furnished by customer

For additional assistance selecting the proper products for your application, see the electronic Buck & Boost Transformer Calculator, available on www.SquareD.com under Free Software and Online Tools.

See Bulletin 7414PD9301 for application tables and wiring diagrams for buck and boost transformers.



PE2

          

Discount

Schedule

9/8/03 © 2005 Schneider Electric
All Rights Reserved
 
Table of Contents Previous Page Next Page Product Index

Square D US
Telemecanique US
Merlin Gerin US