Automatic low voltage capacitor banks are ideally suited for power factor correction at the main service entrance, in applications where plant loading is constantly changing. A microprocessor-based reactive power controller measures plant power factor via a single CT located on the bus/cable at the main service entrance terminal compartment, and switches capacitor stages in and out of service to track a user-selected target power factor. CT sold separately. Refer to CT Selection Guide on page 4-26. The AV4000 and AV5000 Automatic Capacitor Banks are designed for use in networks that contain little or no current or voltage harmonics.
Advanced Safety Features: The modularized compact design consists of a microprocessor-based controller with capacitor switching modules fitted into a cubicle arrangement for top entry. All power and control wiring is dead front construction. Capacitor modules consist of 3 phase dry metalized polypropylene elements. Each element has a nonreplaceable 100,000 AIR fuse and pressure sensitive interrupter. Capacitor modules feature a pre-charge circuit to reduce switching transients to 20% of that seen with standard capacitor banks. Internal discharge resistors reduce capacitor voltage to 50 Volts or less within 60 seconds. Dead front fuse holders on AV4000 & AV5000 have integral blown fuse indicators, standard. Cubicles are constructed with a locking door as standard and are furnished in a textured powder paint finish, color ASA 49 gray.
State-of-the-art Microprocessor-based Control Module: The solid state control module boasts the following:
![]() |
Automatic C/K ratio selection |
![]() |
Automatic CT polarity retrieval |
![]() |
Automatic phase rotation polarity retrieval |
![]() |
Integral display of target/actual PF, number of steps energized, and more |
![]() |
Simple, menu-driven programming |
![]() |
Stage release at voltage dropout |
![]() |
Alarm relay |
![]() |
Manual operation with automatic return |
![]() |
Comprehensive alarms |
kVAR Rating |
Steps
(Qty x kVAR)
|
Standard Lugs Provided (Qty x AWG)
|
Standard Lugs Provided (Qty x AWG)
|
Circuit Breakere
(BV only)
Frame/Sensor
|
Nominal Current
60 Hzi
(Amps)
|
||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
Catalog No.f
|
Price
|
Encl.g
|
Catalog No.f
|
Price
|
Encl.g
|
||||||
240 Volta |
|||||||||||
50
| 4 x 12.5
| $15001.
| 2
| 2 x 500 MCM
|
. . .
| . . .
| . . .
| 4 x 500 MCM
|
. . .
| 120.3
| |
75
| 3 x 25
| 18392.
| 2
| $24535.
| 2
| 1200/600
| 180.4
| ||||
100
| 4 x 25
| 21783.
| 2
| 27925.
| 2
| 1200/600
| 240.6
| ||||
125
| 2 x 12.5, 4 x 25
| 25173.
| 2
| 31593.
| 3
| 1200/800
| 300.7
| ||||
150
| 6 x 25
| 28564.
| 2
| 38607.
| 3
| 1200/1000
| 360.8
| ||||
175
| 1 x 25, 3 x 50
| 31955.
| 2
| 41997.
| 3
| 1200/1000
| 421.0
| ||||
200
| 2 x 25, 3 x 50
| 38968.
| 3
| 4 x 500 MCM
|
45388.
| 3
| 4 x 500 MCM
|
1200/1000
| 481.1
| ||
225
| 1 x 25, 4 x 50
| 42358.
| 3
| 51353.
| 3
| 1200/1000
| 541.3
| ||||
250
| 5 x 50
| 45749.
| 3
| 54743.
| 3
| 1200/1000
| 601.4
| ||||
275
| 1 x 25, 5 x 50
| 49140.
| 3
| 58134.
| 3
| 1200/1000
| 661.5
| ||||
300
| 6 x 50
| 52530.
| 3
| 61525.
| 3
| 1200/1000
| 721.7
| ||||
480 Volth |
|||||||||||
50
| 2 x 25
| $12422.
| 2
| 2 x 500 MCM
|
$13317.
| 2
| 4 x 500 MCM
|
1200/600
| 60.1
| ||
75
| 1 x 25, 1 x 50
| 13744.
| 2
| 14639.
| 2
| 1200/600
| 90.2
| ||||
100
| 2 x 25, 1 x 50
| 15813.
| 2
| 16743.
| 2
| 1200/600
| 120.3
| ||||
125
| 1 x 25, 2 x 50
| 17133.
| 2
| 18063.
| 2
| 1200/600
| 150.4
| ||||
150
| 3 x 50
| 18454.
| 2
| 24596.
| 2
| 1200/600
| 180.4
| ||||
175
| 1 x 25, 3 x 50
| 20523.
| 2
| 26699.
| 2
| 1200/600
| 210.5
| ||||
200
| 4 x 50
| 21845.
| 2
| 2 x 500 MCM
|
28020.
| 2
| 4 x 500 MCM
|
1200/600
| 240.6
| ||
225
| 1 x 25, 4 x 50
| 23914.
| 2
| 30090.
| 2
| 1200/600
| 270.6
| ||||
250
| 5 x 50
| 25234.
| 2
| 31410.
| 2
| 1200/600
| 300.7
| ||||
275
| 1 x 25, 5 x 50
| 27303.
| 2
| 37104.
| 3
| 1200/600
| 330.8
| ||||
300
| 6 x 50
| 28624.
| 2
| 38668.
| 3
| 1200/800
| 360.8
| ||||
350
| 1 x 50, 3 x 100
| 32015.
| 2
| 42057.
| 3
| 1200/1000
| 421.0
| ||||
400
| 2 x 50, 3 x 100
| 39028.
| 3
| 4 x 500 MCM
|
45720.
| 3
| 4 x 500 MCM
|
1200/1000
| 481.1
| ||
450
| 1 x 50, 4 x 100
| 42418.
| 3
| 51385.
| 3
| 1200/1000
| 541.3
| ||||
500
| 2 x 50, 4 x 100
| 45808.
| 3
| 54802.
| 3
| 1200/1000
| 601.4
| ||||
550
| 1 x 50, 5 x 100
| 49199.
| 3
| 58193.
| 3
| 1200/1000
| 661.5
| ||||
600
| 6 x 100
| 52588.
| 3
| 61583.
| 3
| 1200/1000
| 721.7
| ||||
AV4000 Series The AV4000 Series performs similarly to the AV5000 series and is more economical making it suitable for applications requiring less kVAR (200 kVAR max., 480 V, main lugs, top entry only).
kVAR Rating @ 480 V
|
Steps
(Qty x kVAR)
|
Main Lugsc – NEMA Type 1
|
Standard Lugs Provided (Qty x AWG)
|
Nominal Current
60 Hzi
(Amps)
|
||
|---|---|---|---|---|---|---|
Catalog No.f
|
Price
|
Encl.g
|
||||
50
| 2 x 25
| $11038.
| 1
| 2 x 500 MCM
|
48.1
| |
75
| 1 x 25, 1 x 50
| 12403.
| 1
| 72.2
| ||
100
| 2 x 25, 1 x 50
| 14276.
| 1
| 96.2
| ||
125
| 1 x 25, 2 x 50
| 15641.
| 1
| 120.3
| ||
150
| 2 x 25, 2 x 50
| 17513.
| 1
| 2 x 500 MCM
|
144.3
| |
175
| 1 x 25, 3 x 50
| 18880.
| 1
| 168.4
| ||
200
| 4 x 50
| 20246.
| 1
| 192.5
| ||
The Power Factor Table Calculator, available on www.SquareD.com under Free Software and Online Tools, can be used to determine the capacitor kVAR required to improve PF of a single load or entire power system.
| 9/8/03 | © 2005 Schneider Electric All Rights Reserved |
![]() |
||||||
|
|