Schneider Electric Brands
Page 4-22
click here to download PDF version
Download PDF

 Square D > On-line Catalog > Products > Power Monitoring and Control > LV Standard Automatic Capacitor Banks
Search     
Table of Contents Previous Page Next Page Product Index


Main Lugs and Main Breaker Class 5830

LV Standard Automatic Capacitor Banks

Standard Automatic Capacitor Banks

Automatic low voltage capacitor banks are ideally suited for power factor correction at the main service entrance, in applications where plant loading is constantly changing. A microprocessor-based reactive power controller measures plant power factor via a single CT located on the bus/cable at the main service entrance terminal compartment, and switches capacitor stages in and out of service to track a user-selected target power factor. CT sold separately. Refer to CT Selection Guide on page 4-26. The AV4000 and AV5000 Automatic Capacitor Banks are designed for use in networks that contain little or no current or voltage harmonics.

Features:

Advanced Safety Features: The modularized compact design consists of a microprocessor-based controller with capacitor switching modules fitted into a cubicle arrangement for top entry. All power and control wiring is dead front construction. Capacitor modules consist of 3 phase dry metalized polypropylene elements. Each element has a nonreplaceable 100,000 AIR fuse and pressure sensitive interrupter. Capacitor modules feature a pre-charge circuit to reduce switching transients to 20% of that seen with standard capacitor banks. Internal discharge resistors reduce capacitor voltage to 50 Volts or less within 60 seconds. Dead front fuse holders on AV4000 & AV5000 have integral blown fuse indicators, standard. Cubicles are constructed with a locking door as standard and are furnished in a textured powder paint finish, color ASA 49 gray.

State-of-the-art Microprocessor-based Control Module: The solid state control module boasts the following:

Automatic C/K ratio selection
Automatic CT polarity retrieval
Automatic phase rotation polarity retrieval
Integral display of target/actual PF, number of steps energized, and more
Simple, menu-driven programming
Stage release at voltage dropout
Alarm relay
Manual operation with automatic return
Comprehensive alarms
 

AV5000 Series  3 Phase/60 Hz  Main Lugs or Main Circuit Breaker – CT sold separately. See page 4-26.b
kVAR
Rating
Steps
(Qty x kVAR)
Main Lugsc
NEMA Type 1d
Standard Lugs
Provided
(Qty x AWG)
Main Circuit Breakerc
NEMA Type 1d
Standard Lugs
Provided
(Qty x AWG)
Circuit Breakere
(BV only)
Frame/Sensor
Nominal Current
60 Hzi
(Amps)
Catalog No.f
Price
Encl.g
Catalog No.f
Price
Encl.g
240 Volta
50  
4 x 12.5  
$15001.  
2  
2 x 500 MCM  
. . .  
. . .  
. . .  
4 x 500 MCM  
. . .  
120.3  
75  
3 x 25  
18392.  
2  
$24535.  
2  
1200/600  
180.4  
100  
4 x 25  
21783.  
2  
27925.  
2  
1200/600  
240.6  
125  
2 x 12.5, 4 x 25  
25173.  
2  
31593.  
3  
1200/800  
300.7  
150  
6 x 25  
28564.  
2  
38607.  
3  
1200/1000  
360.8  
175  
1 x 25, 3 x 50  
31955.  
2  
41997.  
3  
1200/1000  
421.0  
200  
2 x 25, 3 x 50  
38968.  
3  
4 x 500 MCM  
45388.  
3  
4 x 500 MCM  
1200/1000  
481.1  
225  
1 x 25, 4 x 50  
42358.  
3  
51353.  
3  
1200/1000  
541.3  
250  
5 x 50  
45749.  
3  
54743.  
3  
1200/1000  
601.4  
275  
1 x 25, 5 x 50  
49140.  
3  
58134.  
3  
1200/1000  
661.5  
300  
6 x 50  
52530.  
3  
61525.  
3  
1200/1000  
721.7  
480 Volth
50  
2 x 25  
$12422.  
2  
2 x 500 MCM  
$13317.  
2  
4 x 500 MCM  
1200/600  
60.1  
75  
1 x 25, 1 x 50  
13744.  
2  
14639.  
2  
1200/600  
90.2  
100  
2 x 25, 1 x 50  
15813.  
2  
16743.  
2  
1200/600  
120.3  
125  
1 x 25, 2 x 50  
17133.  
2  
18063.  
2  
1200/600  
150.4  
150  
3 x 50  
18454.  
2  
24596.  
2  
1200/600  
180.4  
175  
1 x 25, 3 x 50  
20523.  
2  
26699.  
2  
1200/600  
210.5  
200  
4 x 50  
21845.  
2  
2 x 500 MCM  
28020.  
2  
4 x 500 MCM  
1200/600  
240.6  
225  
1 x 25, 4 x 50  
23914.  
2  
30090.  
2  
1200/600  
270.6  
250  
5 x 50  
25234.  
2  
31410.  
2  
1200/600  
300.7  
275  
1 x 25, 5 x 50  
27303.  
2  
37104.  
3  
1200/600  
330.8  
300  
6 x 50  
28624.  
2  
38668.  
3  
1200/800  
360.8  
350  
1 x 50, 3 x 100  
32015.  
2  
42057.  
3  
1200/1000  
421.0  
400  
2 x 50, 3 x 100  
39028.  
3  
4 x 500 MCM  
45720.  
3  
4 x 500 MCM  
1200/1000  
481.1  
450  
1 x 50, 4 x 100  
42418.  
3  
51385.  
3  
1200/1000  
541.3  
500  
2 x 50, 4 x 100  
45808.  
3  
54802.  
3  
1200/1000  
601.4  
550  
1 x 50, 5 x 100  
49199.  
3  
58193.  
3  
1200/1000  
661.5  
600  
6 x 100  
52588.  
3  
61583.  
3  
1200/1000  
721.7  

 

AV4000 Series The AV4000 Series performs similarly to the AV5000 series and is more economical making it suitable for applications requiring less kVAR (200 kVAR max., 480 V, main lugs, top entry only).


AV4000 Series  480 Volth  3 Phase/60 Hz  Main Lugs Only – CT sold separately. See page 4-26.b
kVAR
Rating
@ 480 V
Steps
(Qty x kVAR)
Main Lugsc – NEMA Type 1
Standard Lugs
Provided
(Qty x AWG)
Nominal Current
60 Hzi
(Amps)
Catalog No.f
Price
Encl.g
50  
2 x 25  
$11038.  
1  
2 x 500 MCM  
48.1  
75  
1 x 25, 1 x 50  
12403.  
1  
72.2  
100  
2 x 25, 1 x 50  
14276.  
1  
96.2  
125  
1 x 25, 2 x 50  
15641.  
1  
120.3  
150  
2 x 25, 2 x 50  
17513.  
1  
2 x 500 MCM  
144.3  
175  
1 x 25, 3 x 50  
18880.  
1  
168.4  
200  
4 x 50  
20246.  
1  
192.5  

a For 208 Volt applications, the effective kVAR rating at 208 Volts is 0.75 times the kVAR rating at 240 Volts. See page 4-25 for Medium Voltage Systems.
b A Single remote Current Transformer must be located on the bus/cable at the main service entrance terminal compartment. CT sold separately. Refer to CT Selection Guide on page 4-26.
c Order Only. Typical Delivery—4 to 6 weeks
d NEMA Type 3R and 12 enclosures available, please contact your nearest Square D/Schneider Electric sales office for pricing.
e All trip modules are equipped with dial pick-up settings.
f Top entry is standard. For bottom entry, consult your nearest Square D/Schneider Electric sales office.
g For dimensions, see page 4-26.
h For 600 V equipment, additional sizes, ratings or options, please consult your nearest Square D/Schneider Electric sales office.
i Nominal 60 Hz capacitor current draw based on indicated kVAR and voltage ratings. Consult all applicable electric codes for proper sizing of cables and upstream disconnect.

The Power Factor Table Calculator, available on www.SquareD.com under Free Software and Online Tools, can be used to determine the capacitor kVAR required to improve PF of a single load or entire power system.



DE2C

          

Discount
Schedule

9/8/03 © 2005 Schneider Electric
All Rights Reserved
 
Table of Contents Previous Page Next Page Product Index

Square D US
Telemecanique US
Merlin Gerin US