LV Dry Fixed Unfused Power Factor Correction Capacitors

Class 5810

Low Voltage Fixed Capacitors

Reactivar® fixed low voltage capacitors are ideally suited for power factor correction applications where the load does not change or where the capacitor is switched with the load, such as the load side of a motor starter. Reactivar fixed capacitors are best suited for applications where there are no harmonic currents or voltages present.
For Fixed Capacitors suitable for use in harmonic-rich environments, contact your nearest Square D/Schneider Electric sales office.

Features:
Environmentally Safe: Reactivar capacitors are constructed with a dry type metalized Poly-propylene capacitor element with no liquid dielectrics. There is no risk of fluid leakage or environmental pollution and no need for a drip pan.
Multiple Protection System: The patented protection system incorporates an internal protection device which negates the need for external fuses. Capacitor elements are encased in a non-flammable vermiculite filler as an added safety feature.
Low Loss, Long Life: The design features less than 0.5W/kVAR losses, including discharge resistors.
Attractive finish: Capacitor units feature a textured powder paint finish, ASA 49 gray. Units are constructed of 18 gauge steel and are suitable for floor or wall mounting.

Application Note: Capacitors are a low impedance path for the harmonic currents produced by variable frequency drives, motor soft starters, welders, computers, PLCs, robotics and other electronic equipment. These harmonic currents can be drawn into the capacitor causing it to overheat, shortening its life. Furthermore, the resonant circuit formed by shunt capacitors coupled with system inductances (motors and transformers) can amplify harmonic currents and voltages in the electrical network. This amplification can cause nuisance fuse operation and/or damage to electrical equipment including capacitors and other electronic devices. If power factor correction in the presence of harmonics is required, please contact your nearest Square D/Schneider Electric sales office for assistance.


Unfused 208 and 240 Volt 3 Phase/60 Hz
kVAR Rating
Unfused INDOOR
NEMA Type 1/12a
Unfused OUTDOOR
NEMA Type 3Ra
Rated Current
(Amperes)
Recommended
Wire Size
Recommended Minimum Size Protection Ratinge
Fuse
Circuit Breaker Trip
@ 240 V
@208 V
Catalog Numberb
Price
Encl.c
Catalog Numberb
Price
Encl.c
@240 V
@208 V
(Qty X AWG)
@240 V
@208 V
@240 V
@208 V
2.5  
1.88  
$ 612.  
1  
$ 643.  
1R  
6  
6  
14  
10  
10  
15  
15  
3.5  
2.63  
639.  
1  
671.  
1R  
9  
8  
14  
15  
15  
15  
15  
4  
3.00  
666.  
1  
699.  
1R  
10  
9  
14  
20  
15  
15  
15  
5  
3.75  
731.  
1  
767.  
1R  
13  
11  
12  
20  
20  
20  
20  
6  
4.50  
791.  
1  
830.  
1R  
15  
13  
12  
25  
25  
25  
20  
7.5  
5.63  
851.  
1  
893.  
1R  
19  
16  
10  
30  
30  
30  
25  
10  
7.50  
1025.  
1  
1076.  
1R  
25  
21  
8  
40  
35  
40  
35  
12.5  
9.38  
1218.  
1  
1279.  
1R  
31  
27  
8  
50  
45  
45  
40  
15  
11.25  
1411.  
1  
1481.  
1R  
37  
32  
8  
60  
60  
60  
50  
17.5  
13.13  
1584.  
2  
1662.  
2R  
43  
37  
6  
70  
60  
70  
60  
20  
15.00  
1755.  
2  
1843.  
2R  
49  
42  
6  
80  
70  
80  
70  
22.5  
16.88  
1923.  
2  
2049.  
2R  
55  
47  
4  
90  
80  
90  
70  
25  
18.75  
2067.  
3  
2170.  
3R  
61  
53  
4  
100  
90  
90  
80  
27.5  
20.63  
2715.  
3  
2851.  
3R  
67  
58  
3  
125  
100  
100  
90  
30  
22.50  
3363.  
3  
3531.  
3R  
73  
63  
3  
125  
125  
125  
100  
35  
26.25  
3680.  
4  
3865.  
4R  
85  
73  
2  
150  
125  
150  
125  
40  
30.00  
4162.  
5  
4370.  
5R  
97  
84  
1/0  
175  
150  
150  
125  
45  
33.75  
5072.  
7  
5422.  
7R  
109  
94  
1/0  
200  
175  
175  
150  
50  
37.50  
6167.  
7  
6475.  
7R  
121  
105  
2/0  
200  
175  
200  
175  
60  
45.00  
6656.  
7  
6989.  
7R  
145  
126  
3/0  
250  
200  
225  
200  
70  
52.50  
6999.  
8  
7349.  
8R  
169  
146  
4/0  
300  
250  
300  
225  
75  
56.25  
7229.  
10  
7591.  
10R  
181  
157  
250 kcmil  
300  
300  
300  
250  


Unfused 480 Voltd 3 Phase/60 Hz
kVAR
Rating
Unfused INDOOR NEMA Type 1/12
Unfused OUTDOOR NEMA Type 3Ra
Rated
Current
Recommended
Wire Size
Recommended Minimum Size Protection Ratinge
Fuse
Circuit Breaker Trip
@480 V
Catalog Numberb
Price
Encl.c
Catalog Numberb
Price
Encl.c
@480 V
(Qty X AWG)
@480 V
@480 V
2.5  
$ 558.  
1  
$ 586.  
1R  
3  
14  
5  
15  
4  
580.  
1  
609.  
1R  
5  
14  
10  
15  
5  
595.  
1  
625.  
1R  
6  
14  
10  
15  
6  
619.a  
1  
650.  
1R  
7.2  
14  
15  
15  
7.5  
642.  
1  
674.  
1R  
9  
14  
15  
15  
10  
718.  
1  
755.  
1R  
12  
12  
20  
20  
12.5  
810.  
1  
851.  
1R  
15  
10  
25  
25  
15  
886.  
1  
930.  
1R  
18  
10  
30  
30  
17.5  
937.a  
1  
983.  
1R  
21  
10  
35  
35  
20  
986.  
1  
1036.  
1R  
24  
8  
40  
40  
22.5  
1033.a  
1  
1085.  
1R  
27  
8  
45  
45  
25  
1103.  
2  
1158.  
2R  
30  
8  
50  
45  
27.5  
1169.a  
2  
1228.  
2R  
33  
8  
60  
50  
30  
1234.  
2  
1296.  
2R  
36  
8  
60  
55  
35  
1401.  
3  
1472.  
3R  
42  
6  
70  
65  
40  
1572.  
3  
1651.  
3R  
48  
6  
80  
75  
45  
1679.a  
4  
1763.  
4R  
54  
4  
90  
85  
50  
1784.  
4  
1873.  
4R  
60  
4  
100  
90  
60  
2650.  
5  
2782.  
5R  
72  
3  
125  
125  
70  
2853.a  
5  
2996.  
5R  
84  
2  
150  
150  
75  
2956.  
5  
3104.  
5R  
90  
1  
150  
150  
80  
3130.a  
6  
3286.  
6R  
96  
1/0  
175  
150  
90  
3478.a  
6  
3651.  
6R  
108  
1/0  
200  
175  
100  
3825.  
6  
4017.  
6R  
120  
2/0  
200  
200  
125  
4765.a  
9  
5003.  
9R  
150  
4/0  
250  
225  
150  
5704.a  
9  
5990.  
9R  
180  
250 kcmil  
300  
300  
175  
6374.a  
11  
6692.  
11R  
210  
300 kcmil  
350  
350  
200  
7043.a  
11  
7395.  
11R  
240  
(2) 2/0  
400  
400  
225  
7833.a  
12  
8224.  
12R  
270  
(3) 3/0  
500  
450  
250  
8622.a  
13  
9052.  
13R  
300  
(2) 4/0  
500  
450  
275  
9410.a  
13  
9881.  
13R  
330  
(2) 4/0  
550  
500  
300  
10199.a  
13  
10709.  
13R  
360  
(2) 250 kcmil  
600  
550  

a Order only. Typical delivery is 1 to 2 weeks.
b Wall mounting brackets available for units up to 40 kVAR. Order catalog # PFCDBR1  ($50.00).
c For dimensions, see page 4-21.
d For 600 V equipment, change first digit in catalog number from 4 to 6 (e.g. PFCD6004) and use the same price as above 480 V equipment. See page 4-25 for Medium Voltage Fixed Banks.
e Consult local Electrical Codes for proper sizing of molded case circuit breaker frame and disconnect switch rating and cabling.


DE2C

          

Discount
Schedule

9/8/03 © 2005 Schneider Electric
All Rights Reserved
 
Table of Contents Previous Page Next Page Product Index

Square D US
Telemecanique US