Protection zone: S, T, M, G, B
Specific power system requirements
Feature
|
Digit = Description
|
|---|---|
a. Power supply
| U = Standard
|
b. Second languagea
|
F = French (std)
|
S = Spanish
| |
c. Connector
|
V = Volt (std for B21/B22)
|
C = Current (std for Others)
| |
L = Low power CT (LPCT)
| |
d. Terminations
Main block
|
R = Ring lug type blocks (std)
|
S = Clamping screw type
|
Applicationd |
Specific Power System Requirements |
UMIb |
Price
|
|||||||
|---|---|---|---|---|---|---|---|---|---|---|
General Purpose |
Long Feeder |
Mains in Parallel |
Closed feeder/ main loop |
Typical radial bus |
Generator/ Utilities |
|||||
Metered Valuesc |
||||||||||
B21 (Bus/Voltage)
|
X
| V
|
Advanced
| $2264.
| ||||||
X
| Basic
| 1953.
| ||||||||
B22 (Bus/Voltage)
|
X
| V
|
Advanced
| 2576.
| ||||||
X
| Basic
| 2266.
| ||||||||
G40 (generator)
|
X
| V,I,P,E
|
Advanced
| 3920.
| ||||||
X
| Basic
| 3609.
| ||||||||
M20 (motor)
|
X
| I
|
Advanced
| 2319.
| ||||||
X
| Basic
| 2009.
| ||||||||
M41 (motor)
|
X
| V,I,P,E
|
Advanced
| 3594.
| ||||||
X
| Basic
| 3283.
| ||||||||
S20 (feeder/main)
|
X
| I
|
Advanced
| 1794.
| ||||||
X
| Basic
| 1483.
| ||||||||
S40 (feeder/main)
|
X
| V,I,P,E
|
Advanced
| 3023.
| ||||||
X
| Basic
| 2713.
| ||||||||
S41(feeder/main)
|
X
| V,I,P,E
|
Advanced
| 3439.
| ||||||
X
| Basic
| 3129.
| ||||||||
S42 (feeder/main)
|
X
| X
| V,I,P,E
|
Advanced
| 3870.
| |||||
X
| X
| Basic
| 3559.
| |||||||
T20 (transformer)
|
X
| I
|
Advanced
| 1957.
| ||||||
X
| Basic
| 1647.
| ||||||||
T40 (transformer)
|
X
| V,I,P,E
|
Advanced
| 3272.
| ||||||
X
| Basic
| 2961.
| ||||||||
T42 (transformer)
|
X
| X
| V,I,P,E
|
Advanced
| 4118.
| |||||
X
| X
| Basic
| 3808.
| |||||||
Catalog Number |
Description
|
Price
|
|---|---|---|
Digital I/O module, rear mount |
||
10 Input/4 output
| $616.00
| |
Communications module, DIN mount, external 24 Vdc needed |
||
RS485 Two wire interface modulef
| 398.00
| |
RS485 Four wire interface modulef
| 398.00
| |
Analog I/O modules (3 max.) max. 10 m total cable (daisy chain) |
||
8 RTD input modulek
| 719.00
| |
Analog output module (1 variable) (1 module max.)
| 637.00
| |
Remote advanced UMI for use with SP1xxxB units
| 719.00
| |
Assembly platel
| 131.00
| |
2 ft cable from remote display to base unit
| 36.20
| |
2 m cable from remote display to base unit
| 51.00
| |
4 m cable from remote display to base unit
| 78.00
| |
Ground measurement CT |
||
Interposing window CT—30 mm window
| 116.00
| |
Ground sensor CT—120 mm window
| 235.00
| |
Ground sensor CT—200 mm window
| 378.00
| |
Aux. CT—ground sensor CT ratio adjust (for retrofit)
| 709.00
| |
LPCT test options |
||
LPCT test plug
| 362.00
| |
LPCT injection adaptor
| 3467.00
| |
Software kit |
||
Setting/operating software kitg
| 543.00
| |
Spare parts for Sepam Digital Relay |
||
Screw terminal 20 point terminal blockh
| 43.50
| |
Ring lug 20 point terminal blockh
| 36.20
| |
Screw terminal 6 point terminal blockj
| 36.20
| |
Ring lug 6 point terminal blockj
| 67.00
| |
1 or 5 A CT current connectorh
| 191.00
| |
LPCT current connectorh
| 430.00
| |
VT Voltage connector (Series 20 only)h
| 398.00
| |
Cable for PC to relay connectioni
| 67.00
| |
Cable—communication module to relay connectionf
| 67.00
| |
1. Digital I/O requirements (modules mount on rear of relay unit and require no cable.)
a. Base Unit = 3 configurable outputs and 1 watchdog output (Trip, inhibit close, and send block upstream for Zone Sequence Interlock scheme.)
b. MES114 = 4 additional outputs and 10 inputs (order this module for circuit breaker status, trip circuit supervision, closing, upstream receive for ZSI scheme).
2. Analog I/O requirements (Choose up to 3 of modules <a,b,c> below connected for daisy chain less than 10 m in length using pre-formed RJ45 patch cables in <d>).
a. MET1482 = 8 RTD inputs configurable for PT100, NI 120, NI 100; (Series 20 = 1 module; Series 40 = 2 modules max.)
b. MSA141 = Analog output configurable for 1 variable and 0–20, 4–20, 0–10 mA
c. DSM303 = Remote advanced UMI for use with SP1xxxB units
d. Cables for daisy chaining analog I/O from rear port of relay unit
CCA770 = 0.6 m long
CCA772 = 2 m long
CCA774 = 4 m long
e. AMT840 = Surface mounting bracket for SP1xxxB when used with DSM303.
3. Communications requirements
a. ACE9492 = 2-wire RS485 module, cable-connected to green rear port on relay
b. ACE959 = 4-wire RS485 module, cable-connected to green rear port on relay (CCA612 cable included, 24 Vdc external control power required for both modules.)
4. Ground fault measurement CTs
a. Ground sensor CT direct low-level input to Sepam relay (select window size)
b. Auxiliary window CT for vendor ground sensor CT or residual of phase CTs with 1 A/5 A secondary
c. Auxiliary CT for ratio matching existing ground sensor CT.
5. Setting, configuration, operation and diagnostic software
a. SFT2841 kit = off-line setting file management and on-line operation and diagnostics softwares (includes waveform viewing software SFT2826) and 2 m PC-to-relay cable CCA783.
6. Additional options for LPCT testing, etc. and spares are included in Accessories Selection and Pricing table.
| 9/8/03 | © 2005 Schneider Electric All Rights Reserved |
![]() |
||||||
|
|